For models: 1275H,440381
Smoke and Fire Alarm
User’s Guide
A.C. Wire-in Single and/or Multiple Station (24 Devices) Ionization Smoke
Alarm with 9 Volt Battery Back Up and “HUSH” Control to temporarily
silence nuisance alarms.
Thank you for purchasing this smoke and fire alarm. It is an important
part of your family’s home safety plan. You can trust this product to
provide the highest quality safety protection. We know you expect noth-
ing less when the lives of your family are at stake.
For your convenience, write down the following information.
If you call our Consumer Hotline, these are the first questions
you will be asked.
Smoke Alarm Model Number (located on back of alarm):
Date Code (located on back of alarm). The National Fire Protection
Association (NFPA) and the manufacturer recommend replacing this alarm
ten years from the date code:
Date of Purchase:
Where Purchased:
This product is designed to detect products of combustion using the ionization technique. It contains
0.9 microcurie of Americium 241, a radioactive material. Distributed under U.S. NRC License No. 32-
23858-01E. Manufactured in compliance with U.S. NRC safety criteria in 10 CFR 32.27. The pur-
chaser is exempt from any regulatory requirements.
•
•
•
•
•
For mobile home installation, select locations carefully to avoid thermal barriers that may form at the
ceiling. For more details, see MOBILE HOME INSTALLATION below.
When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm) from the side wall (see
Diagram A).
WARNING! REMOVAL OF THE SMOKE ALARM BATTERY AND DISCONNECTING OR LOSS
OF A.C. POWER WILL RENDER THE SMOKE ALARM INOPERATIVE.
When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a mini-
mum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see Diagram A).
ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm (maximum 80mA for originating unit
with 24 devices interconnected).
Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or room is more
than 30 feet (9.1 m) long.
IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND KEEP THIS MANUAL
NEAR THE ALARM FOR FUTURE REFERENCE.
Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft (0.9m) of the highest
point (measured horizontally). NFPA 72 states: “Smoke alarms in rooms with ceiling slopes greater
than 1 foot in 8 feet (.3m in 2.4 m) horizontally shall be located on the high side of the room.” NFPA
72 states: “A row of detectors shall be spaced and located within 3 ft (0.9m) of the peak of the ceil-
ing measured horizontally” (see diagram “C”).
CONTENTS OF THIS MANUAL
1 -- RECOMMENDED LOCATIONS FOR SMOKE ALARMS
2 -- LOCATIONS TO AVOID
3 -- INSTALLATION INSTRUCTIONS
4 -- OPERATION AND TESTING
5 -- NUISANCE ALARMS
6 -- MAINTENANCE
7 -- LIMITATIONS OF SMOKE ALARMS
8 -- GOOD SAFETY HABITS
9 -- NRC INFORMATION
10 -- NFPA PROTECTION STANDARD 72
11 -- CALIFORNIA STATE FIRE MARSHAL REQUIRED INFORMATION
12 -- SERVICE AND WARRANTY
This smoke alarm uses an extremely small amount of radioactive element in the ionization chamber
(see Section 9). Do not try to repair the smoke alarm yourself. Refer to the instructions in Section 12
for service.
●Smoke Alarms for Minimum Protection
● Smoke Alarms for Additional Protection
● Ionization Type Smoke Alarms with
“Hush” Control or Photoelectric Type
DIAGRAM “B”
ANYWHERE
IN THIS AREA
1. RECOMMENDED LOCATIONS FOR ALARMS
Locate the first alarm in the immediate area of the bedrooms. Try to protect the exit path as the
bedrooms are usually farthest from the exit. If more than one sleeping area exists, locate additional
alarms in each sleeping area.
3 ft
3 ft
(0.9m)
DIAGRAM “A”
(0.9m)
•
HORIZONTAL DISTANCE
FROM PEAK
DIAGRAM “C”
•
•
•
•
Locate additional alarms to protect any stairway as stairways act like chimneys for smoke and heat.
Locate at least one alarm on every floor level.
MOBILE HOME INSTALLATION
Mobile homes built in the past five to seven years have been designed to be energy efficient. Install
smoke alarms as recommended above (refer to RECOMMENDED LOCATIONS and Diagram A).
Locate an alarm in every bedroom.
Locate an alarm in every room where electrical appliances are operated (i.e. portable heaters or
humidifiers).
In mobile homes that are not well insulated compared to present standards, extreme heat or cold can
be transferred from the outside to the inside through poorly insulated walls and roof. This may create a
thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. In such
units, install the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 4” (10
cm) and a maximum of 12” (30.5 cm) below the ceiling (see Diagram A).
•
•
Locate an alarm in every room where someone sleeps with the door closed. The closed door may
prevent the alarm from waking the sleeper.
Smoke, heat, and combustion products rise to the ceiling and spread horizontally. Mounting the
smoke alarm on the ceiling in the center of the room places it closest to all points in the room.
Ceiling mounting is preferred in ordinary residential construction.
If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and
ceiling are either hot or cold, install the alarm on an inside wall. For minimum protection, install at least
one alarm close to the bedrooms. For additional protection, see SINGLE FLOOR PLAN in Diagram B.
WARNING: TEST YOUR SMOKE ALARM OPERATION AFTER R.V. OR MOBILE HOME VEHICLE
HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE.
•
•
Figure 1 illustrates interconnection wiring. Improper connection will result in damage to the alarm,
failure to operate, or a shock hazard.
Make certain alarms are wired to a continuous (non-switched) power line. NOTE: Use standard UL
listed household wire (18 gauge or larger as required by local codes) available at all electrical supply
stores and most hardware stores.
2. LOCATIONS TO AVOID
•
•
•
•
•
•
•
In the garage. Products of combustion are present when you start your automobile.
Less than 4” (10cm) from the peak of an “A” frame type ceiling.
In an area where the temperature may fall below 40ºF or rise above 100ºF.
In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.
In very humid areas. Moisture or steam can cause nuisance alarms.
In insect-infested areas.
FIGURE 1 INTERCONNECT WIRING DIAGRAM
Smoke alarms should not be installed within 3 ft (.9m) of the following: the door to a kitchen, the door
to a bathroom containing a tub or shower, forced air ducts used for heating or cooling, ceiling or whole
house ventilating fans, or other high air flow areas.
•
•
Kitchens. Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have
an alarm silence feature or be a photoelectric type.
Optional Accessory
Near fluorescent lights. Electronic “noise” may cause nuisance alarms.
WIRES ON ALARM HARNESS
CONNECTED TO
Black
White
Red
Hot Side of A.C. Line
Neutral Side of A.C. Line
Interconnect Lines (Red Wires) of Other
Units in the Multiple Station Set up
3. INSTALLATION INSTRUCTIONS
WIRING REQUIREMENTS
•
This smoke alarm should be installed on a U.L. listed or recognized junction box. All connections
should be made by a qualified electrician and must conform to article 760 of the U.S. National
Electrical Code, NFPA 72 and/or any other codes having jurisdiction in your area.
BATTERY INSTALLATION
See MAINTENANCE (Section 6) for battery installation.
•
The appropriate power source is 120 Volt A.C. Single Phase supplied from a non-switchable circuit
which is not protected by a ground fault interrupter.
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COM-
PARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE A.C. QUICK CON-
NECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT ATTACH TO THE
TRIM RING (SEE SECTION 6, FIGURE 6).
WIRING INSTRUCTIONS FOR A.C. QUICK CONNECT HARNESS
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.
•
For alarms that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING.
Leave the red wire insulating cap in place to make certain that the red wire cannot contact any
metal parts or the electrical box.
MOUNTING INSTRUCTIONS
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!
•
•
When alarms are interconnected, all interconnected units must be powered from a single circuit.
1. Remove the trim ring from the back of the alarm by holding the trim ring and twisting the alarm in
the direction indicated by the “OFF” arrow on the alarm cover.
A maximum of 24 Lifesaver devices may be interconnected in a multiple station arrangement. The
interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18
alarms total (smoke, heat, carbon monoxide, etc.) With 18 alarms interconnected, it is still possible
to interconnect up to a total of 6 remote signaling devices and/or relay modules.
2. After selecting the proper smoke alarm location as described in Section 1 and wiring the A.C.
QUICK CONNECT harness as described in the WIRING INSTRUCTIONS, attach the trim ring to the
electrical box (see Figure 2).
3. Use a screwdriver to punch out only the pair of holes in the trim ring that match your type of electri-
cal box or plaster ring. Mount the trim ring to the electrical box, using the appropriate holes. NOTE:
Use the circle, square and octagon markings near each mounting hole in the trim ring to help you
select the correct mounting holes (see Figure 2).
•
•
When mixing models which have battery backup (1275, 1275H, 1285, PE 120, HD135F) with mod-
els without battery backup, (1235, 120X, SL177I) be advised that the models without battery back-
up will not respond during an AC power failure.
The maximum wire run distance between the first and last unit in an interconnected system is 1000
feet.
4. Pull the A.C. QUICK CONNECTOR through the center hole in the trim ring and mount the ring, mak-
ing sure that the mounting screws are positioned in the small ends of the keyholes before tightening
the screws (see Figure 2).
5. Plug the A.C. QUICK CONNECTOR into the back of the alarm (see Figure 3), making sure that the
locks on the connector snap into place. Then push the excess wire back into the electrical box
through the hole in the center of the trim ring.
4. OPERATION AND TESTING
OPERATION: The smoke alarm is operating once A.C. power is applied, fresh batteries are installed
and testing is complete. When the smoke alarm ionization chamber senses products of combustion,
the horn will sound a loud (85db) temporal alarm until the sensing chamber is cleared of smoke parti-
cles.
6. If you have finished all the WIRING, BATTERY INSTALLATION AND TRIM RING MOUNTING STEPS,
you can install the alarm on the trim ring. Alignment marks are provided on the side of the alarm
and on the trim ring (see Figure 4).
7. Install the alarm on the trim ring with the indicating marks aligned and rotate the alarm in the direc-
tion of the “ON” arrow on the cover until the alarm snaps in place (see Figure 4).
HUSH CONTROL: The “HUSH” feature has the capability of temporarily desensitizing the alarm circuit
for approximately 7 minutes. This feature is to be used only when a known alarm condition, such as
smoke from cooking, activates the alarm. The smoke alarm is desensitized by pushing the “HUSH”
button on the smoke alarm cover. If the smoke is not too dense, the alarm will silence immediately
and “chirp” every 30 -40 seconds for approximately 7 minutes. This indicates that the alarm is in a
temporarily desensitized condition. The smoke alarm will automatically reset after approximately 7 min-
utes and sound the alarm if particles of combustion are still present. The “HUSH” feature can be used
repeatedly until the air has been cleared of the condition causing the alarm. Pushing the test/reset but-
ton on the alarm will end the hush period.
8. Turn on the A.C. power. The green A.C. Power On Indicator should be lit when the alarm is operat-
ing from A.C. power.
FIGURE 2. SELECT CORRECT MOUNTING HOLES ON TRIM RING
NOTE: DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEATURE AND SOUND A CON-
TINUOUS ALARM.
CAUTION: BEFORE USING THE ALARM HUSH FEATURE, IDENTIFY THE SOURCE OF THE
SMOKE AND BE CERTAIN A SAFE CONDITION EXISTS.
LED INDICATORS: This smoke alarm is equipped with red and green LED indicators. The red LED is
located under the test button and has two modes of operation.
Rectangular Plaster Ring
Circular Plaster Ring
Octagonal Electrical Box
Standby Condition
Alarm Condition
The red LED will flash every 30-40 seconds to indicate that the smoke
alarm is operating properly.
When the alarm senses products of combustion and goes into alarm,
the red LED will flash rapidly (one flash per second). The rapid flashing
LED and pulsating alarm will continue until the air is cleared.
TAMPER RESIST LOCKING PIN: To make your smoke alarm somewhat tamper resistant, a locking
pin has been provided with your alarm. Using this pin will deter children and others from removing the
alarm from trim ring. To use the pin, insert it into the hole in the side of the alarm after the alarm has
been installed on the trim ring (see Figure 5)
NOTE the tamper resist pin will have to be removed in order to change the batteries. Use a long nose
pliers to pull the pin out of the hole. It is now possible to remove the alarm from the trim ring.
WHEN UNITS ARE INTERCONNECTED, only the red LED of the alarm which senses the smoke or is
being tested (the originating unit) will flash rapidly. All other units in the interconnect system will sound
an alarm but their red LED’s will NOT flash rapidly.
Alignment marks
To remove A.C.
connector,
The green LED is located under the “Hush” button and has two modes of operation.
Tamper resistant
locking pin
squeeze
locking arms
and pull
Standby Condition
Alarm Condition
The green LED will be steady on, indicating the presence of AC power.
This smoke alarm is equipped with an alarm memory which provides a
visual indication when an alarm has been activated. A flashing green LED
indicates the memory condition. The memory will remain activated until it is
reset by pushing the test button.
Install
Remove
In an interconnected installation only the memory of the originating alarm will be activated.
FIGURE 3.
FIGURE 4.
FIGURE 5.
TESTING: Test by pushing the test button on the cover and hold it down for a minimum of 2 seconds.
This will sound the alarm if all the electronic circuitry, horn and battery are working. If no alarm sounds,
check the fuse or circuit breaker supplying power to the alarm circuit. If the alarm still does not sound,
the unit has defective batteries or other failure. DO NOT use an open flame to test your alarm, you
could damage the alarm or ignite combustible materials and start a structure fire.
After installation, TEST your alarm by pressing and holding the test button for several seconds, or by
blowing smoke into the alarm. This should sound the alarm.
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION. Erratic or low sound coming from
your alarm may indicate a defective alarm, and it should be returned for service (see Section 12).
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM REPLACEMENT.
5. NUISANCE ALARMS
Carbon-zinc type
Alkaline type
EVEREADY 216 OR 1222; GOLD PEAK 1604P OR 1604S
EVEREADY 522; DURACELL MN1604, MX1604; GOLD PEAK 1604A
ULTRALIFE U9VL
Smoke alarms are designed to minimize nuisance alarms. Cigarette smoke will not normally set off the
alarm, unless the smoke is blown directly into the alarm. Combustion particles from cooking may set
off the alarm if the alarm is located close to the cooking area. Large quantities of combustible particles
are generated from spills or when broiling. Using the fan on a range hood which vents to the outside
(non-recirculating type) will also help remove these combustible products from the kitchen.
Lithium type
NOTE: REGULAR TESTING IS RECOMMENDED!
Model 1275H has a “HUSH” button that is extremely useful in a kitchen area or other areas prone to
nuisance alarms. For more information, refer to Section 4 OPERATION AND TESTING.
NOTE: IF AFTER BATTERY REPLACEMENT THE ALARM CONTINUES TO CHIRP, PUSH THE TEST
BUTTON. THE “HUSH” FEATURE MAY HAVE BEEN ACTIVATED ACCIDENTLY WHILE CHANGING
THE BATTERY AND PUSHING THE TEST BUTTON WILL END THE HUSH CYCLE.
If the alarm does sound, check for fires first. If a fire is discovered, get out and call the fire department.
If no fire is present, check to see if one of the reasons listed in Section 2 may have caused the alarm.
WARNING! BE SURE TO FOLLOW BATTERY INSTALLATION INSTRUCTIONS PRINTED ON THE
INSIDE OF THE BATTERY DOOR AND USE ONLY THE BATTERIES SPECIFIED. USE OF DIFFERENT
BATTERIES MAY HAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM.
6. MAINTENANCE
ALARM REMOVAL
CLEANING YOUR ALARM.
YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR
IF TAMPER RESIST PIN HAS BEEN USED, REFER TO TAMPER RESIST LOCKING PIN IN SEC-
TION 3 FOR PIN REMOVAL INSTRUCTIONS.
To clean your alarm, remove it from the mounting bracket as outlined in the beginning of this section. You
can clean the interior of your alarm (sensing chamber) by using compressed air or a vacuum cleaner hose
and blowing or vacuuming through the openings around the perimeter of the alarm. The outside of the
alarm can be wiped with a damp cloth. After cleaning, reinstall your alarm and test your alarm by using
the test button. If cleaning does not restore the alarm to normal operation the alarm should be replaced.
To replace the battery, remove the alarm from the trim ring by rotating the alarm in the direction of the
“OFF” arrow on the cover (see Section 3, Figure 4) To disconnect the A.C. power harness, squeeze the
locking arms on the sides of the Quick Connector while pulling the connector away from the bottom of
the alarm (see Section 3, Figure 3).
After cleaning, reinstall your alarm. Test your alarm by using the test button and check that the green
LED is on.
BATTERY INSTALLATION AND REMOVAL
To replace or install the batteries, you must first remove the alarm from the trim ring by following the
ALARM REMOVAL instructions at the beginning of this section. After alarm has been removed, you can
open the battery door and install or replace the battery. Battery installation instructions are provided on
the inside of the battery door.
7. LIMITATIONS OF SMOKE ALARMS
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY
When installing the battery, press the battery reminder finger down into the battery compartment and
install the battery (see Figure 6).
•
NFPA 72 states: Life safety from fire in residential occupancies is based primarily on early notification to
occupants of the need to escape, followed by the appropriate egress actions by those occupants. Fire
warning systems for dwelling units are capable of protecting about half of the occupants in potentially
fatal fires. Victims are often intimate with the fire, too old or young, or physically or mentally impaired
such that they cannot escape even when warned early enough that escape should be possible. For
these people, other strategies such as protection-in-place or assisted escape or rescue are necessary.
•
Smoke alarms are devices that can provide early warning of possible fires at a reasonable cost; how-
ever, alarms have sensing limitations. Ionization type alarms offer a broad range of fire sensing capabil-
ities but are better at detecting fast flaming fires than slow smoldering fires. Photoelectric alarms sense
smoldering fires better than flaming fires. Home fires develop in different ways and are often unpre-
dictable. Neither type of alarm (photoelectric or ionization) is always best, and a given alarm may not
always provide warning of a fire.
FIGURE 6.
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COM-
PARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE A.C. QUICK CON-
NECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT ATTACH TO THE
TRIM RING.
•
•
A battery powered alarm must have a battery of the specified type, in good condition and installed properly.
A.C. powered alarms will not operate if the A.C. power has been cut off, such as by an electrical fire or
an open fuse.
This smoke alarm uses a 9V carbon backup battery (alkaline and lithium batteries may also be used). A
fresh battery should last for one year under normal operating conditions.
•
•
Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are in good
operating condition.
This alarm has a low/missing battery monitor circuit which will cause the alarm to “chirp” approximately
every 30-40 seconds for a minimum of seven (7) days when the battery gets low. Replace the battery
Smoke alarms cannot provide an alarm if smoke does not reach the alarm. Therefore, smoke alarms
when this condition occurs.
may not sense fires starting in chimneys, walls, on roofs, on the other side of a closed door or on a dif-
ferent floor.
9. NRC INFORMATION
Ionization type smoke alarms use a very small amount of a radioactive element in the sensing chamber to
enable detection of visible and invisible combustion products. The radioactive element is safely contained
in the chamber and requires no adjustments or maintenance. This smoke alarm meets or exceeds all
government standards. It is manufactured and distributed under license from the U.S. Nuclear Regulatory
Commission.
•
•
If the alarm is located outside the bedroom or on a different floor, it may not wake up a sound sleeper.
The use of alcohol or drugs may also impair one’s ability to hear the smoke alarm. For maximum pro-
tection, a smoke alarm should be installed in each sleeping area on every level of a home.
•
•
Although smoke alarms can help save lives by providing an early warning of a fire, they are not a sub-
stitute for an insurance policy. Home owners and renters should have adequate insurance to protect
their lives and property.
10. NFPA REQUIRED PROTECTION
Install and maintain Fire extinguishers on every level of the home and in the kitchen, basement and
garage. Know how to use a fire extinguisher prior to an emergency.
The National Fire Protection Association’s Standard 72 provides the following information:
Smoke alarms shall be installed outside each separate sleeping area in the immediate vicinity of the bed-
rooms and on each additional story of the family living unit, including basements and excluding crawl
spaces and unfinished attics. In new construction, a smoke alarm also shall be installed in each sleeping
room.
8. GOOD SAFETY HABITS
DEVELOP AND PRACTICE A PLAN OF ESCAPE
Smoke Detection - Are More Smoke Alarms Desirable? The required number of smoke alarms might not
provide reliable early warning protection for those areas separated by a door from the areas protected by
the required smoke alarms. For this reason, it is recommended that the householder consider the use of
additional smoke alarms for those areas for increased protection. The additional areas include the base-
ment, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required
smoke alarms. The installation of the smoke alarms in the kitchen, attic (finished or unfinished), or garage
is normally not recommended, as these locations occasionally experience conditions that can result in
improper operation.
•
Make a floor plan indicating all doors and windows and at least two (2) escape routes from each room.
Second story windows may need a rope or chain ladder.
•
•
•
Have a family meeting and discuss your escape plan, showing everyone what to do in case of fire.
Determine a place outside your home where you all can meet if a fire occurs.
Familiarize everyone with the sound of the smoke alarm and train them to leave your home when they
hear it.
This equipment should be installed in accordance with the National Fire Protection Association’s Standard
72 (NFPA, Batterymarch Park, Quincy, MA 02269).
•
Practice a fire drill at least every six months. Practice allows you to test your plan before an emer-
gency. You may not be able to reach your children. It is important they know what to do.
NOTIFY YOUR LOCAL FIRE DEPARTMENT AND INSURANCE COMPANY OF YOUR SMOKE ALARM
INSTALLATION.
WHAT TO DO WHEN THE ALARM SOUNDS
•
Leave immediately by your escape plan. Every second counts, so don’t waste time getting dressed or
picking up valuables.
11. CAUTION (AS REQUIRED BY THE CALIFORNIA STATE FIRE
MARSHAL)
“Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows. A smoke alarm installed in each separate sleeping area (in the vicinity of, but
outside of the bedrooms), and heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens,
hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages.”
•
In leaving, don’t open any inside door without first feeling its surface. If hot, or if you see smoke seep-
ing through cracks, don’t open that door! Instead, use your alternate exit. If the inside of the door is
cool, place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke rush
in.
•
•
•
•
Stay close to the floor if the air is smoky. Breathe shallowly through a cloth, wet if possible.
Once outside, go to your selected meeting place and make sure everyone is there.
Call the fire department from your neighbor’s home - not from yours!
12. SERVICE AND WARRANTY
If after reviewing this manual you feel that your smoke alarm is defective in any way, do not tamper with
the unit. Return it for servicing to: KIDDE Safety, 1394 South Third St., Mebane, NC 27302.
1-800-880-6788 (See Warranty for in-warranty returns)
Don’t return to your home until the fire officials say that it is all right to do so.
There are situations where a smoke alarm may not be effective to protect against fire as stated in the NFPA
Standard 72. For instance:
a) smoking in bed
b) leaving children home alone
c) cleaning with flammable liquids, such as gasoline
Further information on fire safety can be obtained in a pamphlet titled “IN A FIRE SECONDS
COUNT” published by the NFPA, Batterymarch Park, Quincy, MA 02269
|