LST Smoke Alarm 5351TE User Manual

Thermal Max Detector  
5351TE  
• Addressable conventional technology  
• Alarm temperature 58°C  
• Addressing by means of address  
module or detector parameterisation  
• Remote readout of detector condition  
• Function testable with Remote Test  
Unit ECO1000RTU  
Description  
The Thermal Max Detector 5351TE recognises a ma-  
ximum temperature of 58°C as sign of fire. It complies  
with Class A2S and can be used up to a room height  
of 6m.  
is displayed on the Zonal Display Unit S300ZDU.  
A test activation of the detector can be carried out  
using the Remote Test Unit ECO1000RTU. In addition  
to the test activation of the detector, the Remote Pro-  
gramming and Test Unit S300RPTU can also be used  
to set and display the following detector parameters:  
• the detector address, and  
Addressable conventional technology is used for alarm  
transmission to the fire detection control panel. The  
detector addressing can be achieved in 2 ways:  
• A detector with an Address Module NG58-1 can be  
individually identified by the suitable control panel.  
• An address, which has been stored in the detector  
by means of the Remote Programming and Test Unit,  
• the date of the previous maintenance.  
The detector can be attached to various types of ba-  
ses and it can be protected against theft.  
Specifications  
Operating voltage  
Current consumption  
Alarm temperature  
Operating temperature  
Ambient temperature  
Relative humidity  
Dimensions ø × H  
Colour  
Supply through the detector line voltage  
typ. 85µA (quiescent)  
58°C  
max. +45°C  
-30°C to +70°C (continuous operation)  
5 – 95% (no condensation)  
102 × 43 (mm)  
cream  
Weight  
75g  
Approval  
LPCB 199n Issue9  
Order number  
Order name  
242042  
Thermal Max Detector/Conv./300/SS 5351TE  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
5351TE_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

La Crosse Technology Clock 306 605 User Manual
La Crosse Technology Portable Radio WS 9016U User Manual
LG Electronics Computer Monitor 42PM1M User Manual
LG Electronics Washer WM2688H User Manual
Life Fitness Treadmill Treadmill User Manual
Lochinvar Water Heater CH CF 991 2071 User Manual
Lux Products Thermostat P111 User Manual
Magnadyne Car Stereo System M5000CD User Manual
Masterbuilt Charcoal Grill 20040211 User Manual
Metra Electronics Car Stereo System 95 3305 User Manual