• Extends fire detection control panels
Series BC016 to 16 detector lines in
addressable conventional technology
• Individual detector addressing with
optional address module
• Individual setting of detector zone
function
• Lines monitored for wire breakage,
short circuit, and short to earth
Description
With the Detector Zone Extension MGE8-1 the fire de- Depending on the type of detector (manual call point,
tection control panel Series BC016 can be extended automatic fire detector with or without alarm verificati-
from 8 to 16 addressable detector zones. Up to 64 on, fault message contacts as well as contacts for tech-
detectors (addresses) per detector line can be indivi- nical messages), the function of the detector zone can
dually identified with the aid of an address module. In be set separately for each detector line. Each input of
the event of an alarm, the fire detection control panel the Detector Zone Extension is protected against over-
indicates the number of the detector that triggers the voltage and thus provides high system stability.
alarm first.
Specifications
Current consumption at 24V
Line voltage
typ. 32mA (8 zones terminated, without detectors)
typ. 20.0V
Line current
typ. 3.8mA
End-of-line resistance
Line resistance
Ambient temperature
Dimensions L × W × H
Weight
5.6kΩ or 3,3kΩ (depending on setup)
max. 50Ω per core
-5°C to +50°C
100 × 65 × 15 (mm)
80g
Part No.
210110
Order name
Detector Zone Extension MGE8-1
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
MGE8-1_DBL_LST_EN_0804.PDF • PAGE 1