Liebert Active Tracking Filter System
Technical Specification
Operating Voltage Range......................................... +/-15%
Fault Current Rating (AIC)........................................ 200 kAIC
Operating Frequency Range.................................... 47 – 63 Hz
50 EMI/RFI Attenuation:
Normal Mode .............................................. 10 kHz-500MHz 60 dB
Common Mode ........................................... 10 kHz-500MHz 50 dB
Response Time ......................................................... <0.5 ns
Operating Humidity................................................... 0% to 95%
Status Indication....................................................... LEDs, Dry Contacts, Audible Alarm,
Surge Counter
Certifications............................................................. UL 1449 & 1283, CSA
Enclosure .................................................................. NEMA 12 standard
Warranty .................................................................... 10-Years Parts / 5-Years Labor
Optional Equipment.................................................. Dual Surge Counter,
Remote Monitor Panel
Example Part Number: F277Y800-03 = 277/480V, 3-Phase Wye, All Mode, 800 Amp Current Rating
LED’s, Alarm & Dual Counters, Form C Contacts
Life Cycle Surge Testing
10kA, 20kV, IEEE Cat. C3
F__ __ __ __ __ __ __ __ - __ __
Unit
Per Mode (L-N/L-G/N-G)
Per Phase
100 kA
150 kA
200 kA
300 kA
12,000/12,000/12,000
12,000/24,000/24,000
24,000/24,000/24,000
24,000/48,000/48,000
24,000
36,000
48,000
72,000
Nominal
Voltage Codes
Option Code
LED, Form C
01
03
06
Contacts
120
208
220
230
240
277
480
600
120V
208V
220V
230V
240V
277V
480V
600V
LED, Alarm, Dual
Counters, Form C
Contacts
LED, Alarm, Counter,
Form C Contacts
UL 1449 second edition clamping data
Voltage
100-120V
208V
230-277V
347V
L-N
400
L-G
400
L-L
800
800
1500
2000
1500
2000
N-G
400
800
800
800
700
1000
1200
1000
1500
2000
400-480V
600V
Source configuration
1 Phase L-N 2w + gnd
1 Phase L-L 2w + gnd
Split Phase 3w + gnd
3 Phase Wye 4w + gnd
3 Phase Delta 3w + gnd
3 Phase Delta Hi-leg 4w+ gnd
Dimensional data in inches and shipping weight in pounds
Model/Configuration Dimensions in inches
N
L
S
Y
D
H
Wt
A
B
C
D
E
F
Lbs
30A Single Phase
20.0
24.0
20.0
24.0
24.0
30.0
24.0
30.0
48.0
60.0
60.0
60.0
60.0
16.0
20.0
16.0
20.0
20.0
24.0
20.0
24.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
21.25
25.25
21.25
25.25
25.25
31.25
25.25
31.25
49.25
-
10.0
14.0
10.0
14.0
14.0
18.0
14.0
18.0
30.0
-
.44
.44
.44
.44
.44
.44
.44
.44
.44
-
35
60
30A Split or Three Phase
60A Single Phase
35
60A Split or Three Phase
100A Single Phase
60
60
100A Split or Three Phase
225A Single Phase
80
Current
Code
30
Current
Rating
30A
Surge Current Capability
Per Phase
100kA
60
225A Split or Three Phase
400A Split or Three Phase
800A Split or Three Phase
1200A Split or Three Phase
2000A Split or Three Phase
4000A Split or Three Phase
80
60
60A
100kA
150kA
150kA
150kA
300kA*
300kA*
300kA*
300kA
36.0 12.0
48.0 12.0
48.0 20.0
48.0 20.0
48.0 20.0
300
530
750
950
1300
100
100A
225
225A
-
-
-
400
400A
800
800A
-
-
-
1200
2000
4000
1200A
2000A
4000A
-
-
-
* 200kA is available,
add –200 to part number.
Job Name____________________________
Model# ______________________________
Date ________________________________
Qty _________________________________
Quote# ______________________________
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169