Calculite® HID A-E
Page 1 of 1
Auxiliary Lighting Systems For Temporary H.I.D. Lamp Outage
Mode of Operation
Auxiliary Lighting for Recessed HID Luminaires and Cylinders (A)
H.I.D. lamps require a “warm-up” period of 5 to 10 minutes to reach full output.
Additionally, when these lamps are extinguished they must cool for 5 to 15
minutes before they will relight. Outage can be caused by momentary power
failure, substantial voltage reduction or cycle changes.
Initial Start:
H.I.D. lamp and tungsten halogen lamp both energized. H.I.D.
lamp starts warming up; tungsten-halogen lamp at full output.
To provide a minimum level of illumination, a double-contact bayonet socket and
solid-state switching device, (for use with a 120V tungsten-halogen lamp) operate
during initial H.I.D. lamp warm-up, or cold-off-and-restart period.
Partial Warm-Up:
H.I.D. lamp reaches approximately 60% light output; tungsten-
halogen lamp switched off.
The tungsten-halogen lamp remains on until the HID lamp reaches approximately
60% of its light output.
Note: The auxiliary is not emergency lighting and will only operate when there is
power to the luminaire. The AUX system is available for magnetic ballast either
120V or 277V branch circuits with a ballast tap supplying 120V to the tungsten-
halogen lamp. 120V electronic ballast can be operated with 120V branch circuit.
For 277V, electronic, consult factory.
Full Warm-Up:
H.I.D. lamps at 100% light output.
To specify: add suffix “A” to Catalog Number for Recessed H.I.D. Fixture.
See fixture specification sheets for compatibility.
“Hot” Restart:
H.I.D. lamp and tungsten-halogen lamp both energized. H.I.D.
lamp too hot to start; tungsten-halogen lamp at full output. After
H.I.D. lamp cools down and starts, cycle begins as in “Initial
Start” above.
Emergency Lighting for Recessed HID Luminaires (E)
A tungsten-halogen lampholder, (without the switching device) prewired with
#18AWG SF2 leads in a 5/16" x 26" long flexible greenfield cable, is provided
with the luminaire for attachment to an AC 60 cycle power supply. Power supply
by others.
To specify: add suffix “E” to Catalog Number for Recessed H.I.D. Fixture.
See fixture specification sheets for compatibility.
Maximum Tungsten-Halogen Lamp Wattage
HID Lamp
Tungsten-Halogen Lamp T-4, 120V
Double-Contact Bayonet
39W-70W T6
150W T6
39W-150W ED17, PAR
175W
75W
75W*
100W
150W
150W
250W-400W
*Applicable for any reflector trim with “CL” finish.