Raypak Outdoor Storage 241355 User Guide

Raypak Glass-Lined Storage Tank  
Installation & Maintenance Procedures  
Flushing the Storage Tank  
NOTE: The information contained in this manual is  
intended for use by qualified professional installers,  
service technicians or gas suppliers. Consult your  
local expert for proper installation or service proce-  
dures.  
Since the mineral accumulation is occurring in an un-  
fired tank it will be in a soft sediment form. Much of this  
soft sediment can be removed by a regular flushing of  
the lower portion of the tank.  
Installation  
To flush the tank, follow these steps:  
The water storage tank MUST be installed using di-  
electric connections. Failure to do so will void the man-  
ufacturer’s warranty. Installation of the tank without  
dielectric connections can cause the rapid failure of the  
storage tank due to electrolysis. For this reason, it is  
imperative that dielectric connections be utilized.  
1. Turn off the electricity and gas supply to the water  
heater piped to the storage tank.  
2. Turn off electrical power to the circulating pump.  
3. Close the valve on the hot water outlet on the top of  
the storage tank.  
4. Ensure that the drain located on the bottom of the  
tank is routed to a floor drain with adequate  
capacity to allow the tank to be flushed.  
5. Open the drain valve and allow the incoming cold  
water to flush the soft sediment out the bottom of  
the storage tank. Use extreme caution, as the water  
exiting the tank drain may be very hot. Avoid con-  
tact with the hot discharge water to prevent the risk  
of severe scald injury.  
6. Observe the color of the water initially discharged  
from the tank drain. This water will generally be  
milky or slightly discolored by the sediment dis-  
charge. Allow the drain to run until the water runs  
clear.  
7. Close the drain valve on the tank.  
8. Open the hot water outlet valve on the top of the  
tank.  
The tank should be installed in such a manner that  
should the tank or any of its connections leak, the re-  
sulting flow of water will not cause damage.  
Follow the Dielectric Protection instructions in these  
procedures to verify that the dielectric connections are  
installed properly. If electrical continuity exists between  
the tank and its piping, the connections MUST be  
fixed.  
Maintenance  
A new tank installation should have a regular inspec-  
tion program set up initially. The first inspection should  
be within the first three months of operation. Once the  
tendency to accumulate sediment has been estab-  
lished, the inspection program can be modified to suit  
the water conditions. Typical inspection programs flush  
the tank at six-month intervals and clean the tank in  
yearly intervals.  
9. Open an adjacent hot water tap to purge any air  
that may have entered the storage tank during the  
draining process. Close the hot water tap if no air  
discharge is observed.  
10. Turn on electric power to the water heater and cir-  
culating pump.  
11. Turn on the gas supply to water heater.  
12. Observe heater and piping to ensure all compo-  
nents are functioning properly.  
Deliming solvents or acid type flush agents are not rec-  
ommended for use in lined storage tanks. These  
chemical cleaners are usually designed for use in non-  
potable systems such as heating boilers. These chemi-  
cals may be aggressive and cause damage to the tank  
lining and deteriorate the magnesium anodes supplied  
in Raypak glass-lined storage tanks.  
Cleaning the Storage Tank  
The mineral accumulation in an un-fired tank will be in  
a soft sediment form that can be removed by a regular  
cleaning of the lower portion of the tank. Many tanks  
will have a hand hole or a larger manway to allow ac-  
cess to the interior of the tank for complete removal of  
accumulated sediment. The opening will be in the bot-  
WARNING: Hot water will be released under pres-  
sure. Avoid contact with the hot discharge water to  
prevent the risk of severe scald injury.  
CATALOG NO. 4000.50B  
Effective: 12-01-08  
Replaces: 06-02-08  
P/N 241355 Rev. 1  
 

Q Logic Switch 59060 02 B User Guide
Raymarine GPS Receiver ST7002 User Guide
Roberts Radio Radio CRD 39 User Guide
Roland Drums TD 20 User Guide
Samsung Automobile Parts SR 28 29 User Guide
Samsung Computer Drive HM080HJ User Guide
Sanus Systems MP3 Docking Station PFV36SB 01 User Guide
Sanyo Computer Monitor CE52LH1R User Guide
Sanyo Digital Camera IDC 1000ZEX User Guide
Sanyo Flat Panel Television DP52440 User Guide