Toshiba Power Supply 1600 XP UPS User Manual

Quick Installation Guide  
1600XP Series UPS  
Purpose  
This Quick Installation Guide (QIG) provides the minimum information needed to connect and startup your 1600 XP UPS. The  
complete 1600XP Users Manual and supporting documentation are provided in the accompanying CD (P/N 62908). The self-  
starting CD requires a PC with a web browser (e.g Microsoft Explorer) and a PDF file viewer (e.g. Adobe Acrobat Reader).  
If requested, a printed manual may be provided at no cost from Toshiba International Corporation. Contact UPS Marketing at  
800-231-1412.  
NOTE: This QIG is not intended to replace the 1600XP Users Manual.  
Toshiba International Corporation reserves the right, without prior notice, to update information, make product changes, or  
discontinue any product or service identified in this publication.  
Toshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages resulting from the use  
of the information contained within this QIG.  
QUALIFIED PERSONNEL ONLY  
Qualified person is one that has the skills and knowledge relating to the construction, installation, operation, and maintenance  
of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for  
additional safety requirements).  
Qualified personnel shall:  
1. Have read the entire operation manual.  
2. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and equipment, and clear faults  
in accordance with established safety practices.  
3. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety  
glasses, face shields, flash clothing, etc., in accordance with established safety practices.  
4. Be trained in rendering first aid.  
5. Be knowledgeable of batteries and the required handling and maintenance precautions.  
Misuse of this equipment may result in human injury and equipment damage. In no event willToshiba Corporation be responsible  
or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment.  
DO NOT open or mutilate the batteries. Released electrolyte is harmful to the eyes and skin and could also be toxic.  
DO NOT dispose of the battery module in a fire. The batteries inside may explode.  
To be performed by Qualified Personnel Only:  
1. Verify that the UPS is off and that the power is disconnected from the power source.  
2. Remove watches, rings or other metal objects.  
3. Use tools with insulated handles to prevent inadvertent shorts.  
4. Wear rubber safety gloves and boots.  
5. DO NOT place tools or any metal parts on top of batteries.  
Contact with any part of a grounded battery can result in electrical shock.  
The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance.  
62909-000  
1
March 2010  
 
When operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the  
battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be  
in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown  
power to the load.  
Wait at least 5 minutes after an Emergency Power Off (EPO) before resetting the UPS breaker. This  
allows the UPS circuitry to fully discharge. The UPS could be damaged if the unit is not fully discharged  
before the breaker is reset.  
NOTICE  
Hardwire Connections  
Remove the terminal cover plate on the lower-left back side of the UPS. Follow the directions below in wiring the unit.  
Jumper Position for 208V/240V Input, 240/208/120V Output  
12 13 14 15 16 17  
1
2
3
4
5
6
7
8
11  
REMOTE1 REMOTE2  
EPO1 EPO2  
L1 L2  
G
X1 X2  
N
X3  
G
208 COM 240  
120 V  
208 V  
240 V  
120 V  
Jumper  
position  
for 208 V for 240 V  
Jumper  
position  
208/240 Vin  
Jumper Position for 230V Input, 230V Output  
12 13 14 15 16 17  
1
2
3
4
5
6
7
8
11  
REMOTE1 REMOTE2  
L1 (L)  
L2 (N)  
EPO1 EPO2  
G
X1 X2  
N
X3  
G
230 Vin  
230 V  
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with the provided jumper wire/bus bar. DO NOT jumper terminal 13 to  
12 or 11. Factory Setting is 208Vac. Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.  
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with the provided jumper wire/bus bar. DO NOT jumper terminal 11 to  
12 or 13. Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.  
NOTE 3 – 8-22 kVA UPSs have a jumper bus bar.  
Output Terminal Voltages  
Vout  
Terminal Lugs  
X3 - N, X1 - N  
X3 - X2  
Output Terminal Connections  
Connect the load to the output terminals according the load voltage requirements. See  
the Output Terminal Voltages table to the right.  
120 V  
208 V  
240 V  
230 V  
X3 - X1  
Wire Size and Tightening Torque  
Use the following table to select the recommended wire size and terminal lug  
tightening torque for I/O wire connections.  
X3 - X1  
Terminal  
Number  
AWG  
AWG  
AWG  
AWG  
AWG  
AWG  
Tightening Torque  
Item  
3.6 kVA 6 kVA 8 kVA 10 kVA 14-18 kVA 22 kVA  
lb.-in. (N•m)  
AC Input Lines  
1 and 2  
12 (8)  
12 (8)  
12 (8)  
12 (8)  
16  
14.2 (1.56)  
14.2 (1.56)  
14.2 (1.56)  
14.2 (1.56)  
9.0 (0.99)  
9.0 (0.99)  
10 (8) 8 (1/0) 6 (1/0)  
10 (8) 8 (1/0) 6 (1/0)  
10 (8) 8 (1/0) 6 (1/0)  
10 (8) 8 (1/0) 6 (1/0)  
4 (1/0)  
4 (1/0)  
4 (1/0)  
4 (1/0)  
16  
1 (1/0)  
1 (1/0)  
1 (1/0)  
1 (1/0)  
16  
AC Output Lines 4, 5, and 7  
AC Output Neutral  
Ground  
6
3 and 8  
EPO Switch  
14 and 15  
16 and 17  
16  
16  
16  
16  
16  
16  
Remote Switch  
16  
16  
16  
Note: Wire size presented as the recommended size followed by a bold number in () that is the maximum wire size the terminal block can  
accommodate. See the manual, page 48, for knock-out hole sizes on the back of each model.  
1600XP Series Quick Installation Guide  
3
 
Initial UPS Startup  
The first time the UPS is activated after being shipped from the factory, an initialization program will require the  
operator to input the following parameters. The UPS display operation is explained in detail on pages 32-62  
1. The first screen during the initial startup sequence requires the operator to select the nominal input voltage.  
Select from 208V, 230V, or 240V, and press the Write key. If the command has been accepted, the word  
“Successful” will appear at the bottom left side of the display.  
2. Repeat the process in step 1 in selecting the Rated Vout.  
3. Repeat the process in step 1 in selecting the Input Frequency.  
4. Use the keypad to type in the current date in the format: Mon 10/05/2009. and press Write.  
5. Use the keypad to type in the current time in 12 hour format: 12:15 PM and press Write.  
6. The Main screen is now displayed. Verify the UPS is in BYPASS mode. The mode (lower right side of the  
display) should display Bypass. If it does not display Bypass, press and momentarily hold the STOP button.  
7. With the UPS in bypass mode, cycle power to the UPS as follows:  
At the rear of the UPS switch the main circuit breaker MCCB to OFF.  
Leave the UPS off until the DC bus is safely discharged (approximately 5-10 minutes).  
Restart the UPS by switching the main circuit breaker ON.  
The table below summarizes the initialization parameters:  
ID  
Command  
Options  
111  
Rated Vin  
Select from 208V, 230V, or 240V, and press Write.  
Select from 208V, 230V, or 240V, and press Write.  
Select from 60Hz or 50Hz, and press Write.  
215  
141  
634  
635  
Rated Vout  
Input Frequency  
UPS Date  
Input the date in this format: Mon 10/05/2009. and press Write.  
Input the current time in 12 hour format: 12:15 PM and press Write.  
UPS Time  
FAQ Sheet  
Following are some Frequently Asked Questions concerning installation of the 1600EP Series UPS.  
The batteries for the UPS must be installed while the UPS is energized.  
NOTICE  
FAQ #1  
My Output is ~85V.  
Problem: Output is wired across the incorrect output terminals. The voltage across terminals 5 – 6(X2 – N) will  
be approximately 85V.  
Solution: The correct 120V output terminals are 4 – 6 (X1 – N), and 7 – 6 (X3 – N).  
My Output is other than 85, 120, 208 or 240V.  
FAQ #2  
Problem: The Terminal strip jumper may be installed incorrectly for the incoming voltage.  
Solution: Check that the Jumper wire/buss strip is installed correctly for the incoming voltage.  
Toshiba Contact Information: Toshiba Industrial Division, 13131 West Little York Road, Houston, TX 77041  
Tel: US 800-231-1412, Canada 800-872-2192, Mexico 01/800/527-1204 www.toshiba.com/ind  
1600XP Series Quick Installation Guide  
4
 

Targus Network Card USB to Serial Digital Device Adapter User Manual
Tektronix Electronic Keyboard TR 502 User Manual
Tektronix Marine Radio CSA 803C User Manual
Telenetics Network Card MIU Dial or Leased Line modem with RS 485 User Manual
Texas Instruments Computer Drive TMS320F20x F24x DSP User Manual
Topfield TV Receiver TF 7000 HD PVRt User Manual
Trane Thermostat CT30 User Manual
Tricity Bendix Oven BD900 User Manual
Tripp Lite Mouse KP3040 User Manual
Troy Bilt Blower TB197BV User Manual