Universal Security Instruments Smoke Alarm USI 5204 User Manual

Visit Us on the Web! www.SmokeAlarms.com  
USI-5204  
MODEL USI-5204  
(Part #USI-5204HA)  
COMMERCIAL RESIDENTIAL (UTHA)  
SMOKE & FIRE ALARM WITH SILENCE CONTROL  
READ ALL INSTRUCTIONS  
The smoke alarm has a recommended service life of at least 10 years under normal conditions.  
The smoke alarm uses an extremely small amount of a radioactive element in the ionization  
chamber. Do not tamper with radioactive sealed source or try to repair the smoke alarm  
yourself. Refer to instructions for repairs.  
SMOKE ALARM LIMITATIONS AND FUNCTIONS  
THERE ARE TWO BASIC SMOKE ALARM TYPES - IONIZATION AND PHOTOELECTRIC.  
Ionization smoke alarms are your best overall choice for reliability and fast response time,  
since they quickly sense small "invisible" smoke particles and will also sense larger "visible"  
smoke particles. Photoelectric smoke alarms may respond more quickly in certain types of  
fires, for example - slow smoldering fires with large "visible" smoke particles. ALLTYPES OF  
SMOKEALARMS HAVE LIMITATIONS. NO TYPE OF SMOKEALARM CAN SENSE EVERY  
KIND OF FIRE OR SMOKE EVERY TIME.  
WARNING - SMOKEALARMS WILLNOTWORK DURINGALOSS OF POWER. SINCEASMOKE  
ALARM WILL NOT WORK WITHOUT POWER, having an alarm(s) that works from two completely  
different power sources, such as anAC direct wire with battery backup smoke alarm, can give you an  
extra measure of protection in case of anAC power failure or a dead battery.  
USING A SMOKE ALARM IN A SMOKY AREA LIKE A KITCHEN, OR IN A HIGH HUMIDITY  
AREA NEAR A SHOWER, CAN CAUSE FALSE ALARMS. DO NOT TURN OFF THE AC  
POWER TO QUIET THEALARM. ASMOKE ALARM WILL NOT HELP PROTECT YOU IF IT  
IS NOT POWERED. Properly locate your alarm to avoid nuisance alarms.  
ASMOKEALARMMAYNOTALWAYSWARNYOUABOUTFIRESCAUSEDBYCARELESSNESS  
AND SAFETY HAZARDS LIKE SMOKING IN BED, VIOLENT EXPLOSIONS, ESCAPING GAS,  
IMPROPER STORAGE OF FLAMMABLE MATERIALS, OVERLOADED ELECTRICALCIRCUITS,  
CHILDREN PLAYING WITH MATCHES, NATURALCAUSES SUCHAS LIGHTNING, ORARSON.  
FIRE PREVENTION IS YOUR BEST SAFEGUARD.  
INSTALLING SMOKE ALARMS MAY MAKE YOU ELIGIBLE FOR LOWER INSURANCE  
RATES, but SMOKE ALARMS ARE NOT A SUBSTITUTE FOR INSURANCE. Homeowners  
and renters alike should continue to insure their lives and properties.  
SMOKEALARMS CANNOT WORK WITHOUT POWER. Battery operated units cannot work if the  
batteries are missing, disconnected or dead, if the wrong type of batteries are used or if the batteries  
are not installed correctly. AC (only) powered units cannot work if the AC power is cut off for any  
reason. If you are concerned about the limitations of battery orAC power, install both types of units.  
SMOKE ALARMS CANNOT DETECT FIRES IF THE SMOKE DOES NOT REACH THEM.  
Smoke from fires may not reach the sensing chamber and set off the alarm. One unit should  
be installed inside each bedroom or sleeping area.  
SMOKE ALARMS MAY NOT DETECT FIRE ON ANOTHER FLOOR OR AREA OF THE  
HOME. Recommended minimum protection is at least one unit in every sleeping area and  
every bedroom on every level of your home. Interconnected units may provide earlier warning  
than stand-alone units since all units alarm when one detects smoke.  
SMOKEALARMS MAYNOT BE HEARD. The alarm horn in this unit meets or exceeds current  
standards, but it may not be heard if: (1) the unit is located outside a closed or partially closed  
door; (2) residents recently consumed alcohol or drugs; (3) the alarm is drowned out by noise  
from stereos, TV's, air conditioners or other appliances or (4) if residents are hearing impaired  
or sound sleepers.  
SMOKE ALARMS ARE NOT FOOLPROOF. You must test the unit weekly to ensure your  
continued protection. Smoke alarms cannot prevent or extinguish fires.  
SMOKEALARMS HAVEA LIMITED LIFE. The unit should be replaced immediately if it is not  
operating properly. You should always replace a smoke alarm after 10 years.  
SMOKE ALARMS ARE NOT TO BE USED WITH DETECTOR GUARDS UNLESS THE  
COMBINATION HAS BEEN EVALUATED AND FOUND SUITABLE FOR THAT PURPOSE.  
CURRENT STUDIES HAVE SHOWN SMOKEALARMS MAY NOTAWAKENALLSLEEPING  
INDIVIDUALS AND THAT IT IS THE RESPONSIBILITY OF INDIVIDUALS IN THE  
HOUSEHOLD WHOARE CAPABLE OFASSISTING OTHERS TO PROVIDEASSISTANCE  
TO THOSE WHO MAY NOT BE AWAKENED BY THE ALARM SOUND OR TO THOSE  
WHO MAY BE INCAPABLE OF SAFELY EVACUATING THE AREA UNASSISTED.  
 
AVOID THESE LOCATIONS  
the garage – products of combustion are present when you start your automobile.  
near appliances or areas where normal combustion regularly occurs (kitchens, near furnaces,  
gas hot water heaters). Use smoke alarms with Silence Control for these areas.  
in areas with high humidity, like bathrooms or areas near dishwashers or washing machines.  
Install at least 3 feet (0.9 meters) away from these areas.  
in areas of turbulent air such as air returns or heating and cooling supply vents, smoke alarms  
shall not be located where airflow prevents operation of the alarms.  
in extremely dusty, dirty or insect-infested areas. Loose particles interfere with smoke alarm  
operation.  
in areas where temperature may fall below 400F (4.40C) or rise above 1000F (37.80C).  
closer than 1 foot (0.3m) from fluorescent lights, electrical "noise" and flickering may affect the  
alarm's operation.  
closer than 3 feet (0.9m) horizontal path from the tip of the blade of a ceiling suspended (paddle)  
fan.  
on a poorly insulated ceiling or exterior wall (mount smoke alarm on an inside wall).  
THIS SMOKE ALARM WILL NOT WORK WITHOUT 120 VAC POWER AND A  
GOOD BATTERY PROPERLY INSTALLED. THE SMOKE ALARM SHOULD BE  
TESTED WHEN INSTALLED AND THEN TESTED WEEKLY AFTER THAT.  
FALSEALARMS  
The smoke alarm is designed to minimize false alarms. Smoking will not normally set off the alarm  
unless smoke is blown directly into the smoke alarm. Combustion particles from cooking may set  
off the alarm if the smoke alarm is located close to the kitchen cooking surface. Large quantities of  
combustion particles are generated from spills or broiling.  
If the smoke alarm does sound, check for fires first. If a fire is discovered, get out and call the fire  
department. If no fire is present, check to see if one of the reasons listed above may have caused  
the alarm. Use the "silence" feature if it is a false alarm.  
INSTALLATION AND OPERATION  
INSTALLATION INSTRUCTIONS: CAUTION!! READ CAREFULLY.  
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!  
A mounting plate is provided on the back of the alarm.  
Remove the mounting plate from the back of the alarm by holding the mounting plate and twisting  
the alarm in the direction indicated by the "TURN TO REMOVE" arrow on the side of the alarm  
base.  
Installation of this unit must conform to the electrical codes in your area; Article 760 of the  
National Electrical Code, NFPA 72, 101; SBC (SBCCI); UBC (ICBO); NBC (BOCA): OTFDC  
(CABO), and any other local or building codes that may apply. Wiring and installation must  
be performed by a licensed electrician. Failure to follow these guidelines may result in injury  
or property damage.  
This unit must be powered by a 24-hour, 120V AC 60Hz circuit. Be sure the circuit cannot be  
turned off by a switch, dimmer or ground fault circuit interrupter. Failure to connect this unit  
to a 24-hour circuit may prevent it from providing constant protection.  
IMPORTANT: Do not subject this smoke alarm to megger, high voltage or high-pot tests.  
Remove the smoke alarm(s) before high-potting tests occur on the circuit or system.  
(Ref. Section 550-17, National Electric Code, 2002 Edition).  
ELECTRICAL SHOCK HAZARD  
Turn off power to the area where you will install this unit at the circuit breaker or fuse box  
before beginning installation. Failure to turn off the power before installation may result in  
serious electrical shock, injury or death.  
TAMPER LOCKING PIN: To make your alarm somewhat tamper resistant, a locking pin has been  
provided (break-away part of mounting plate). Using this tamper pin will deter children and others  
from removing the alarm from the mounting plate. To use the tamper pin, insert it into the hole in the  
side of the alarm after the alarm has been installed on the mounting plate. Using long nose pliers,  
pull the tamper pin out of the hole. It is now possible to remove the alarm from the mounting plate.  
1. Turn the alarm counterclockwise in the direction indicated by the "TURN TO REMOVE" arrow  
on the side of the alarm base to remove it from the mounting plate. NOTE: The alarm is sealed  
and the cover is not removable.  
Page 3  
 
2. Wiring Instructions:  
a. The appropriate power supply is 120 Volt single phase power supplied from a non-switchable  
circuit NOT protected by a ground fault circuit interrupter.  
b. Turn off main power to the circuit before wiring the smoke alarm.  
c. There are three pigtail leads (black, white and yellow) coming from the AC QUICK  
CONNECTOR. The proper wire connection is as follows:  
WIRES FROM QUICK CONNECTOR  
CONNECT TO  
BLACK  
WHITE  
YELLOW  
"HOT" side of AC line  
"NEUTRAL" side of AC line  
Interconnect wires of other units  
For units that are used as single smoke alarms, do not connect the yellow wire to anything. Insulate  
this wire (tape it) in place to make certain the yellow wire cannot contact any metal parts.  
Interconnected units can provide earlier warning of fire than stand-alone units, especially if  
a fire starts in a remote area of the dwelling. This smoke alarm may be interconnected with  
as many as 11 other USI ELECTRIC model smoke alarms such as USI-1103, USI-1203, USI-  
1204, USI-1209, USI-1213, USI-2204, USI-3204 and 6 other units which may be a combination  
of Carbon Monoxide Alarms such as USI-7385, USI-7390, USI-7485, USI-7490, USI-7795, Heat  
Alarms/USI-2430 or Relay Modules/USI-960 for a total of not more than 18 interconnected  
devices.  
Interconnected CO alarms will only respond if a CO alarm / event initiates the alarm. All other  
alarms remain silent.  
Interconnected smoke alarms, heat alarms and relay modules will only respond if a smoke  
alarm / event or heat alarm / event initiates the alarm. All CO alarms remain silent.  
Note that units without battery backup will not respond during an AC power failure.  
NOTE: Relay Modules/USI-960 will not respond if a CO alarm / event initiates the alarm.  
INPUT:  
120 VAC  
60 HZ  
.05A  
The yellow wire is used only for multiple station operation with USI ELECTRIC Model alarms  
only. Connecting this yellow wire to any other circuits may result in damage. When alarms  
are interconnected, all units must be powered from a single AC branch circuit. If local codes  
do not permit be sure the neutral wire is common to both phases. The maximum wire run  
distance between the first and last alarm/device in an interconnected system is 1,000 feet.  
NOTE: Use standard household wire (18 gauge or larger, rated at least 300V, as required by  
local codes) available at all electrical supply/hardware stores.  
The wiring to be used shall be in accordance with the provisions ofArticles 210 and 300.3(B)  
of the National Electrical Code, ANSI/NFPA70. In addition, the resistance of the interconnecting  
wiring shall be a maximum of 10 Ohms.  
Early warning fire detection is best achieved by the installation of fire detection equipment in  
all rooms and areas of the household as follows: A smoke alarm installed in each separate  
sleeping area (in the vicinity of, but outside of, the bedrooms) and heat or smoke alarms in  
living rooms, dining rooms, kitchens, hallways, attics, furnace rooms, closets, utility storage  
rooms, basements and attached garages. Test the smoke alarm weekly to assure proper  
operation.  
3. Attach the mounting plate to the electrical junction box.  
4. To activate 9 volt battery and alarm, hold the QUICK DRAW(R) battery drawer closed, pull and  
remove the PULL-TAB. Discard PULL-TAB.  
5. Plug the AC QUICK CONNECTOR into the alarm base. Push and turn the alarm clockwise  
onto the mounting plate.  
6. See "TAMPER LOCKING PIN."  
Page 4  
 
7. Turn on AC power and check the LED's for proper operation. The green LED lights to indicate  
AC power. The red LED will flash every 40-60 seconds to indicate proper operation.  
OPERATION, TESTING & MAINTENANCE  
OPERATION: The smoke alarm is operating once the power is connected and turned on (the battery  
must also be installed). When products of combustion are sensed, the unit sounds a loud alarm  
which continues until the air is cleared.  
This alarm incorporates the internationally recognized horn signal for evacuation. During alarm  
mode, the horn produces three short beeps followed by a two second pause and then repeats.  
STANDBY CONDITION: The red LED flashes once every 40-60 seconds to indicate the unit is  
properly functioning.  
LOCAL ALARM CONDITION: The red LED flashes rapidly and the unit emits a loud, pulsating  
alarm sound.  
REMOTE ALARM CONDITION: The red LED is off and the unit emits a loud, pulsating alarm.  
GREEN LED: The green LED is on whenever AC power is turned on.  
TESTING: Test by pushing the test button on the smoke alarm cover until the alarm sounds, then  
release. The alarm sounds if all electronic circuitry, horn and battery are working. The alarm may  
continue to sound for up to 10 seconds after the button is released. If no alarm sounds, the unit may  
have a defective battery or other failure. Test the smoke alarm weekly to assure proper operation.  
NEVER use an open flame of any kind to test this unit. You might accidentally damage or set  
fire to the unit or to your home. The built-in test switch accurately tests the unit's operation  
as required by Underwriters Laboratories Inc. (UL).  
(UTHA) Sensitivity Indicating Means  
The sensitivity indicating means for this Smoke and FireAlarm is the use of the analyzer for Smoke  
Detectors Model 501-A or 501-A/Bat Aerosol Generator Manufactured by Gemini Scientific Corp.,  
1122-B Aster Ave., Sunnyvale, CA 94086.  
The Equivalent UL 268 Light obscuration %/Ft as measured by this instrument must be between  
1.55% Obs./Ft. and 0.85% Obs./Ft (1.20 + 0.35% Obs./Ft.).  
(UTHA) Go/No-Go Field Test  
The Go/No-Go test for this Smoke and FireAlarm is the use of a UL Listed can type aerosol smoke  
detector tester. The instructions for the use of this tester are given on the container.  
If you choose to use an aerosol smoke product to test the smoke alarm, be certain to use one  
that has been Listed to Underwriters Laboratories, Inc. Safety Standards and use it only as  
directed. Use of non-UL Listed products or improper use of UL Listed products may affect  
the smoke alarm's sensitivity.  
FALSE ALARMS "SILENCE" CONTROL: Units with the "silence" feature have the capability of  
temporarily reducing the sensitivity of the alarm circuit for approximately 3-9 minutes. This feature is  
to be used only when a known alarm condition such as smoke from cooking activates the smoke  
alarm. The smoke alarm "silence" feature is activated by pushing the Hold to Silence button on the  
smoke alarm cover for at least three seconds. The smoke alarm will automatically reduce sensitivity  
and the red LED will light for approximately 3-9 minutes to indicate the alarm is in the temporary  
silent condition. The smoke alarm will gradually regain normal sensitivity and sound the alarm if  
particles of combustion are still present. The "silence" feature may be used repeatedly until the air  
has cleared.  
Page 5  
 
Before using the alarm "silence" feature, identify the source of smoke and be certain that  
safe conditions exist.  
(UTHA) MAINTENANCE:  
The smoke alarm is virtually maintenance free. However, under dusty conditions, a vacuum hose  
may be used to clear the sensing chamber of dust.  
Clean the smoke alarm at least once a month to remove dust, dirt or debris.Always turn off power  
to smoke alarm before cleaning. Using a soft brush or wand attachment to a vacuum cleaner,  
vacuum all sides and cover of smoke alarm. Be sure all the vents are free of debris.  
If the smoke alarm is false alarming and cannot be restored to normal operation, the smoke alarm  
should be replaced.  
BACKUP BATTERY REPLACEMENT  
Disconnect AC power before changing battery. Shock hazard exists if AC power is miswired.  
The smoke alarm uses a 9 Volt battery. The battery should last for at least one year under normal  
operating conditions. The smoke alarm has a low battery indicator, an audible "beep." It will operate  
at 30-40 second intervals for a minimum of 7 days. When this indication occurs, replace the battery  
with anAlkaline type (Eveready Energizer #522, Duracell #MN1604), Carbon-Zinc type (Gold Peak  
#1604P, Eveready #216). Use the convenient QUICK DRAW(R) pull-out batterydrawer for easy battery  
replacement.  
Pull the QUICK DRAW(R) battery drawer open and remove the battery. While observing polarity,  
push the replacement battery into the battery drawer until it is held securely in place. Carefully close  
and latch the battery drawer.  
REPAIRS AND SERVICES  
The smoke alarm contains less than 1 microcurie (37 kilobecquerel) ofAmericium 241, a radioactive  
material. The distribution of these ionization-type smoke alarms is licensed by the U.S. Nuclear  
Regulatory Commission; the consumer is exempt from any licensing or requirements. If the  
smoke alarm is defective in any way, do not tamper with the unit. Return the unit for servicing. (See  
warranty for instructions or in-warranty returns.) There will be a service charge for repairing out of  
warranty units.  
Page 6  
 
DEVELOP AND PRACTICE A PLAN OF ESCAPE  
BASICS OF ESCAPE PLAN  
o
Make a floor plan indicating all doors and windows and at least two escape routes from each  
room. Second story windows may need a rope or chain ladder.  
o
Have a family meeting and discuss your escape plan, showing everyone what to do in case of  
fire.  
o
o
Determine a place outside your home where all of you can meet if a fire occurs.  
Familiarize everyone with the sound of the smoke alarm and train them to leave your home when they  
hear the sound.  
o
o
Identify children's bedrooms with red stickers placed in the upper left corner of the windows. They  
are available from your local fire department.  
Practice a fire drill at least every six months. Practice allows you to test your plan before an  
emergency. You may not be able to reach your children. It is important they know what to do!  
WHAT TO DO WHEN THE ALARM SOUNDS  
o
Leave immediately by your plan of escape. Every second counts, so don't waste time getting  
dressed or picking up valuables.  
o
In leaving, don't open any inside door without first feeling its surface. If hot, or if you see smoke  
seeping through cracks, don't open that door! Instead, use your alternate exit. If inside door is  
cool, place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke  
rush in.  
o
o
o
o
Stay close to the floor if air is smoky. Breathe shallowly through a cloth, wet if possible.  
Once outside, go to your selected meeting place and make sure everyone is there.  
Call the fire department from your neighbor's home – not from yours!  
Don't return to your home until fire officials say that it is all right to do so.  
NATIONAL FIRE PROTECTION ASSOCIATION REQUIRED PROTECTION  
For your information, the National Fire Protection Association's Standard 72, reads as follows:  
11.5.1 One- and Two-Family Dwelling Units. 11.5.1.1 Smoke Detection.  
Where required by applicable laws, codes, or standards for the specified  
occupancy, approved single- and multiple-station smoke alarms shall be  
installed as follows: (1) In all sleeping rooms. Exception: Smoke alarms  
shall not be required in sleeping rooms in existing one- and two-family  
dwelling units. (2) Outside of each separate sleeping area, in immediate  
vicinity of the sleeping rooms. (3) On each level of the dwelling unit, including  
basements. Exception: In existing one- and two-family dwelling units,  
approved smoke alarms powered by batteries are permitted.  
“A.11.8.3 Are More Smoke Detectors Desirable? The required number of  
smoke detectors might not provide reliable early warning protection for those  
areas separated by a door from the areas protected by the required smoke  
detectors. For this reason, it is recommended that the householder consider  
the use of additional smoke detectors for those areas for increased  
protection. The additional areas include the basement, bedrooms, dining  
room, furnace room, utility room, and hallways not protected by the required  
smoke detectors. The installation of smoke detectors in kitchens, attics  
(finished or unfinished), or garages is not normally recommended, as these  
locations occasionally experience conditions that can result in improper  
operation.”  
The equipment should be installed using wiring methods in accordance with the National  
Fire Protection Association’s Standard 72, Chapter 11. (National Fire Protection  
Association, Batterymarch Park, Quincy, MA 02269).  
THIS PRODUCT IS LISTED TO UL STANDARD FOR SAFETY,  
UL217 BY UNDERWRITERS LABORATORIES  
Page 7  
 
USI FIVE YEAR LIMITED WARRANTY  
USI ELECTRIC, INC. ("USI") warrants your USI product to be free  
from defects in material and workmanship for a period of five (5)  
years from the date of purchase. This warranty applies only to the  
original consumer purchaser and only to products used in normal  
residential use and service. If this product is found to be defective, USI's  
only obligation, and your exclusive remedy, is the repair or replacement  
of the product, at USI's discretion, provided that the product has not  
been damaged through misuse, abuse, accident, modifications, alteration,  
neglect or mishandling. This Warranty shall not apply to any product  
which is found to have been improperly installed, set-up, or used in any  
way not in accordance with the instructions supplied with the product.  
This warranty shall not apply to any batteries used in the product or to  
any damage which may be caused by such batteries. For repair or  
replacement, send the defective product to USI ELECTRIC, INC. at  
11407 Cronhill Drive, Suite A, Owings Mills, Maryland 21117, postage  
prepaid with a payment of $5.00 to cover the costs of return postage  
and handling. You must include a proof of purchase (receipt) along with  
the returned product.  
USI DOES NOT WARRANT AND SPECIFICALLY DISCLAIMS ANY  
WARRANTY, WHETHER EXPRESS OR IMPLIED, OF FITNESS FOR  
A PARTICULAR PURPOSE, OTHER THAN THE WARRANTY  
CONTAINED HEREIN. NO IMPLIED WARRANTY ON THIS PRODUCT,  
CREATED BY STATE LAW, SHALL EXTEND BEYOND THE TERM OF  
THIS WARRANTY UNLESS SUCH LAW OTHERWISE PROVIDES. USI  
SPECIFICALLY DISCLAIMS ANY LIABILITY AND SHALL NOT BE  
LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL LOSS OR  
DAMAGE, INCLUDING, BUT NOT LIMITED TO, DAMAGES TO ANY  
EQUIPMENT WITH WHICH THIS PRODUCT IS USED.  
Some states do not allow the exclusion or limitation of incidental or  
consequential damages so the above limitations or exclusions may not  
apply to you.  
No agent, representative, dealer, or employee of the company has the  
authority to increase or alter the obligations or terms of this Warranty.  
This Warranty gives you specific legal rights and you may also have  
other rights which vary from state to state.  
This Warranty is only valid for merchandise purchased from outlets in  
the United States and Canada.  
Visit Us on the Web! www.SmokeAlarms.com  
11407 Cronhill Drive, Suite A  
Owings Mills, Maryland 21117 USA  
©2002 UNIVERSAL SECURITY INSTRUMENTS, INC.  
288-3297-00D/UTHA  
Printed in China  
 

Toshiba Barcode Reader B EV4T SERIES User Manual
Toshiba Laptop 5005 User Manual
Toyota Automobile matrix User Manual
Tripp Lite Switch B004 VPA2 K R User Manual
Troy Bilt Brush Cutter P N 769 01473 User Manual
Troy Bilt Tiller 640C Tuffy CRT User Manual
Tunturi Home Gym E85 User Manual
Vivotek Security Camera IP 8332C User Manual
Vizio TV DVD Combo VBR231 User Manual
Vulcan Hart Humidifier VHMD5 User Manual