3M Water System SF1XX User Manual

TM  
3M Water Filtration Products  
Scale Feeder Manifold Water Filtration  
System Instruction Manual  
For SF1XX  
High Flow Series Water Filtration Systems  
Installer: Please leave this manual with owner/operator.  
 
CAUTION  
To reduce the risk associated with property damage due to water leakage:  
• Read and follow Use Instructions before installation and use of this system.  
• Installation and Use MUST comply with all state and local plumbing codes.  
Protect from freezing, remove filter cartridge when temperatures are expected to drop below 40°F (4.4°C);  
• Do not install on hot water supply lines. The maximum operating water temperature of this filter system is  
100°F (37.8°C).  
Do not install if water pressure exceeds 125 psi (862 kPa). If your water pressure exceeds 80 psi (552 kPa),  
you must install a pressure limiting valve. Contact a plumbing professional if you are uncertain how to check  
your water pressure.  
Do not install where water hammer conditions may occur. If water hammer conditions exist, you must  
install a water hammer arrester. Contact a plumbing professional if you are uncertain how to check for this  
condition.  
• Any non-metallic fittings used in the installations must be of adequate rating for the line pressure.  
Do not use a torch or other high temperature sources near filter system, cartridges, plastic fittings or plastic  
plumbing.  
• On plastic fittings, never use pipe sealant or pipe dope. Use PTFE thread tape only, pipe dope properties may  
deteriorate plastic.  
• Take care when using pliers or pipe wrenches to tighten plastic fittings, as damage may occur if overtight-  
ening occurs.  
Do not install in direct sunlight or outdoors.  
Do not install near water pipes which will be in path of a drilling tool when selecting the position to mount  
the bracket.  
• Mount filter in such a position as to prevent it from being struck by other items used in the area of installation.  
• Ensure that the location and fasteners will support the weight of the system (Approx. 10.5 lbs [4.8 kg]) when  
installed and full of water.  
• Ensure all tubing and fittings are secure and free of leaks.  
• The disposable filter cartridge MUST be replaced every 12 months or at the rated capacity or if a noticeable  
reduction in flow rate occurs.  
IMPORTANT NOTES  
• Failure to follow instructions may void warranty.  
• Allow a minimum of 3” (7.6 cm) clear space under filter to facilitate cartridge change.  
• Install with the inlet and outlet ports as labeled. Make sure not to reverse connections.  
• Some local codes may require the use of a licensed plumber or certified installer when disrupting a potable  
water line.  
SF1XX Manifold and ScaleGARD™ HT Systems  
SF1XX High Flow series water filtration systems combine chlorine taste and odor reduction with particulate  
reduction, and help protect equipment from the potentially harmful effects of scale formation, even at application  
temperatures to 200°F (93°C). The inlet water enters the manifold on the left rear side and exits through the scale-  
inhibitor feeder on the right front side. The capacity of the system is equal to the flow rate and capacity rating for  
the filter cartridges used.  
Inlet and Outlet Connections  
The water inlet is on the left rear side and the outlet is on the right front side. These are identified with labels. The  
fitting size is 3/4” NPT (Male). A built-in check valve (non-return) is incorporated into the outlet.  
3
 
Product Dimensions  
17 5/16"  
(44.0 cm)  
5 7/16"  
(13.8 cm)  
18 1/16"  
(45.9 cm)  
Minimum of 3" (7.6 cm)  
For Cartridge Change  
How to Use the Inlet/Outlet Fitting Retention Clips  
This product is outfitted with inlet/outlet fittings. The fittings can be attached or removed from the system  
without tools. Retention clips are semi-circular in shape with three internal tabs, bottom, center and top. Tab interlaces  
with windows in the manifold head near each connection port. Clip is flexible and easily assembled following these  
instruction and illustrations.  
1. Insert fitting into manifold.  
2. With fitting inserted into manifold port, snap clip into place beginning at the bottom window  
3. Push center tab into center window.  
4. Finally push top tab into top window.  
Step 1  
Step 4  
Step 2  
Step 3  
4
 
Equipment Installation  
CAUTION  
To reduce the risk associated with property damage due to water leakage:  
Do not use a torch or other high temperature sources near filter system, cartridges, plastic fittings or plastic  
plumbing.  
• On plastic fittings, never use pipe sealant or pipe dope. Use PTFE thread tape only, pipe dope properties may  
deteriorate plastic.  
• Take care when using pliers or pipe wrenches to tighten plastic fittings, as damage may occur if overtight-  
ening occurs.  
Do not install near water pipes which will be in path of a drilling tool when selecting the position to mount  
the bracket  
• Mount filter in such a position as to prevent it from being struck by other items used in the area of installation.  
• Ensure that the location and fasteners will support the weight of the system when installed.  
• Ensure all tubing and fittings are secure and free of leaks.  
IMPORTANT NOTES  
• Failure to follow instructions may void warranty.  
• Allow a minimum of 3” (7.6 cm) clear space under filter to facilitate cartridge change.  
• Install with the inlet and outlet ports as labeled. Make sure not to reverse connections.  
• Some local codes may require the use of a licensed plumber or certified installer when disrupting a potable water line.  
The SF1XX manifold may be used with metal or non-metallic piping systems.  
CAUTION  
To reduce the risk associated with property damage due to water leakage:  
• Any non-metallic fittings used in the installations must be of adequate rating for the line pressure.  
1. Shut off incoming cold water supply.  
2. Select the installation location. IMPORTANT NOTE: Allow a minimum of 3 in (7.6 cm) of space below the car-  
tridge for change-outs.  
3. Select fasteners (not included) and tools appropriate for the installation location (wall, support structure mount-  
ed to wall studs, concrete, etc.).  
CAUTION  
To reduce the risk associated with property damage due to water leakage:  
• Ensure that the location and fasteners will support the weight of the system (Approx. 10.5 lbs [4.8 kg])  
when installed and full of water.  
4. Mount the manifold/filter system to a wall using the mounting holes provided on the back plate of the metal  
bracket.  
• It is recommended to first draw a level line on the mounting surface at the height of the fasteners.  
• Mark the location of the fasteners using the bracket as a template or by measuring the distance between  
the mounting holes.  
• Install the fasteners and allow 1/4”-3/8” (6-10 mm) of each fastener to protrude from the surface.  
• Install the manifold onto the fasteners.  
• Tighten the fasteners.  
5. Install inlet (left rear) and outlet fittings (right front). All connections terminate with a ¾” NPT (male) fitting. The  
inlet kit includes the fitting and a ball valve. The kit for the right front side outlet includes the fitting, a stainless-  
steel tee, a nipple, a check valve and another nipple. Refer to section “How to Use the Inlet/Outlet Fitting  
Retention Clips” are on page 4. (PTFE tape is not included).  
6. Remove the sanitary caps from the cartridge, and apply a light coat of water or food-grade lubricant to the o-  
rings on each of the cartridges.  
7. Align the tabs of the water filter cartridge with the slots in the retaining plate and insert the cartridge into the  
manifold.  
8. Turn the cartridge to the right until a clicking sound is heard; the clicking sound indicates the cartridge is prop-  
erly engaged.  
9. Install the scale-inhibitor cartridge by engaging the threads in the stainless steel tee and turning to the right  
(clockwise) until snug, regardless of the final label orientation.  
5
 
Equipment Start-up Procedure  
1. Turn on incoming water to system.  
2. Pressurize system by rotating the inlet ball valve handle 1/4 turn counter-clockwise to the “ON” position.  
3. Check for leaks.  
4. Use any downstream vent to remove trapped air.  
5. Flush system in accordance with the Performance Data Sheet for the water filter cartridge. System is now  
ready to use.  
Cartridge Change-out Procedure  
CAUTION  
To reduce the risk associated with property damage due to water leakage:  
• Read and follow Use Instructions before installation and use of this system.  
• Installation and Use MUST comply with all state and local plumbing codes.  
• The disposable filter cartridge MUST be replaced every 12 months or at the rated capacity or if a noticeable  
reduction in flow rate occurs.  
The water filter cartridge will need to be changed every 6-12 months or when low pressure is indicated on the  
manifold’s pressure gauge, whichever occurs first. Depending on local water quality, you may need to change the  
cartridges prior to the recommended change-out.  
1. Shut off the inlet water by rotating the inlet ball valve 1/4 turn clockwise to the “OFF” position.  
2
Depressurize system.  
3. Push tab to release cartridge locking mechanism while simultaneously rotating cartridge slightly to the left.  
4. Using both hands and holding cartridge from the bottom, rotate the cartridge a quarter turn to the left and  
gently pull down. IMPORTANT NOTE: A small amount of water will drain from manifold as cartridge is re-  
moved.  
5. Remove sanitary cap from new cartridge. Install cartridge with a quarter turn to the right until cartridge comes  
to a complete stop.  
6. Remove the small scale inhibitor cartridge by rotating to the left (counterclockwise) until the threads are dis-  
engaged. Replace with a new cartridge by rotating to the right (clockwise) until the threads are fully engaged  
and snug, regardless of final label orientation.  
7. Slowly turn the inlet ball valve on the manifold 1/4 counter-clockwise to the “ON” position and check for  
leaks.  
8. Flush system in accordance with the Performance Data Sheet. System is now ready for use.  
Troubleshooting  
Inlet valve closed  
Check shut-off valve position  
No water flow through system  
Filter clogged  
Replace cartridge  
Low incoming water pressure  
Filter clogged  
Check source  
Not enough water to the  
downstream application(s)  
Replace cartridge  
Short filter life  
Temporarily dirty water  
Change cartridge or install an  
additional upstream pre-filter.  
6
 
Replacement Parts Listing  
Item  
Part no.  
Description  
Qty*  
Function  
1
6228601  
SF1XX Manifold Assembly  
1
Assembly, complete  
HF65 Replacement Cartridge  
for SF165 System  
2a  
2b  
3
56134-07  
1
1
1
Water filtration  
Water filtration  
See Catalog for  
Options  
Replacement Cartridge  
Options  
HF8-S Replacement Car-  
tridge  
5582106  
Scale-inhibitor addition  
4
5
85005-49  
85-8528  
63597320  
6225005  
6225007  
60-235380  
Inquire  
Pressure gauge  
Clip  
1
1
1
1
1
1
1
Monitor outlet water pressure  
Retain inlet/outlet fittings  
Seal inlet/outlet fittings  
Inlet fitting with ball valve  
Outlet to equipment  
6
O-ring  
7
Inlet fitting kit –left rear  
Outlet fitting kit – right front  
3/4” x 3/4” ball valve  
Retainer Kit  
8
9
Inlet water shut-off  
10  
Secure cartridge  
*Per part number, not per system or assembly.  
a
7
 
Limited Warranty  
3M Purification Inc. warrants SF1XX only to be free from defects in material and workmanship for five (5) years from the date of purchase.  
The disposable filter cartridge is warranted from defects in material and workmanship for a period of one (1) year from the date of purchase.  
This warranty does not cover failures resulting from abuse, misuse, alterations or damage not caused by 3M Purification Inc. or failure to follow  
installation and use instructions. No warranty is given as to the service life of any filter cartridge or membrane as it will vary with local water  
conditions and consumption. 3M PURIFICATION INC. MAKES NO OTHER WARRANTIES OR CONDITIONS, EXPRESS OR IMPLIED, INCLUDING,  
BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OR CONDITION OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR ANY  
IMPLIED WARRANTY OR CONDITION ARISING OUT OF A COURSE OF DEALING, CUSTOMER OR USAGE OF TRADE. If the Product fails to satisfy  
this Limited Warranty during the warranty period, 3M Purification Inc., at it’s option, will replace the Product or refund your Product purchase price.  
This warranty does not cover labor. The remedy stated in this paragraph is Customer’s sole remedy and 3M Purification Inc.’s exclusive  
obligation.  
This warranty gives you specific legal rights, and you may have other rights which may vary from state to state, or country to country. For any  
warranty questions, please call 866.990.9785 or mail your request to: Warranty Claims, 3M Purification Inc., 400 Research Parkway, Meriden, CT  
06450. Proof of purchase (original sales receipt) must accompany the warranty claim, along with a complete description of the Product, model  
number and alleged defect.  
Limitation of Liability: 3M Purification Inc. will not be liable for any loss or damage arising from this 3M Purification Inc. product, whether direct,  
indirect, special, incidental, or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability. Some  
states and countries do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not  
apply to you.  
3M Purification Inc.  
400 Research Parkway  
Meriden, CT 06450  
Toll Free: 866.990.9785  
Worldwide: 203.237.5541  
Fax: 203.238.8897  
3M is a trademark of 3M Company.  
ScaleGARD is a trademark of 3M Company used under license  
© 2012 3M Company. All rights reserved.  
INSTR4324 0912B  
Please recycle. Printed in U.S.A.  
 

Acoustic Energy Speaker AELITE Three User Manual
Adesso Computer Keyboard WKB 4400UB User Manual
ADTRAN Server 619510003 1A User Manual
AEG Oven BP5013001M User Manual
Aiphone Home Security System Jb Da User Manual
Aiphone Home Security System JDW C User Manual
Airstream Smoke Alarm NTERSTATE User Manual
Alesis Computer Drive D4 User Manual
Avocent Switch SC 1x4 User Manual
Beko DVD Player DVD 2008 User Manual