Installation Sheet
RDM-2SWMDual Switch Module 20A
Specifications
The RDM-2SWM Dual Switch Module is a 20 A general-purpose relay
module built for the economical switching of incandescent lamps, switched
low-voltage transformers, switched fans, and small motors. It uses positive
air gap relays. The RDM-2SWM is designed for use with the RDA series of
enclosures, in an AMX Lighting™ modular digital dimming system. This
module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.
•
•
•
•
•
•
•
•
•
Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
Non-phase dependant
Use wires rated at 75°C (167°F)
Torque terminals to 7 in-lbs. (0.8 N/M)
Max. wire size: 10 AWG (4 mm²)
Wire stripping length: 0.28" (7 mm)
Weight: 0.75 lbs. (0.34 kg)
Mounting
points
BTU/hr: 5 each, 10 total
Control current: 85 mA per relay (170 mA total) @ 12 VDC
Line in (hot)
Caution: Pre-Installation Notes
•
•
•
•
•
•
•
•
•
•
All Class 1 wiring must be connected to proper terminals.
All control wiring must be connected to proper terminals.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times.
Test loads for shorts before connecting.
Use low-voltage wires with a 300 volt rating or greater.
Use field installed copper conductors.
All electrical ratings are for continuous duty.
High-voltage
connections
Load out
Relay A
Relay B
For indoor use only.
This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDM-2SWM to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-2SWM 4-pin module connector
3 (-)
Low-voltage control wiring:
4-pin connection to AMX
Lighting master controller
1 (+)
4-pin plug from RDM series module
NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).
FIG. 2 RDM-2SWM connections
FIG. 1 RDM-2SWM Dual Switch Module
RDM-2SWM UL and C-UL Ratings (per circuit)
•
•
•
•
General purpose: 2400 W
Resistive: 2400 W
Ballast: 2400 W
Motor: 277 VAC, 1 hp
Suggested Switched Loads
•
•
•
•
•
Incandescent
Low-voltage
Motors
Switched outlets
Fluorescent
|