Air King Ventilation Hood ASLC70 User Manual

SPECIFICATIONS  
ASLC70  
EXHAUST FANS  
70 CFM/4.0 SONES @ 0.10" WG. -HVI CERTIFIED  
120 Volts, 1.6 amps, 60 hz.  
758"  
/
738"  
/
Grill  
White polymeric grill secured in place via screw mounting  
1
/
through the light housing, dimensions - 11" x 10 2".  
4"  
578"  
/
• Light Lens  
High impact polycarbonate lens, secured in position using  
integral tabs; easily removed if necessary.  
• Light Housing  
1012"  
/
Heavy gauge cold rolled steel c/w baked enamel finish; locks  
in place on the grill via two integral tabs.  
11"  
• Blower Wheel  
CUL/HVI  
1
/
One piece polymeric wheel, 4 2" diameter, 1" wide, with 10 fins.  
Acceptable for use over tub or shower when  
installed in a GFCI protected branch circuit.  
• Motor  
Single coil plug-in, two pole motor, life time lubrication, thermally  
protected. Rated 120 volts, 60 hz., 1.6 amps.  
• Unit Mounting  
Rated Type IC for ceilings insulated to R-40. Designed to mount  
in ceilings with at least 6" of clearance. The unit will mount  
directly to the joist or using the supplied mounting bars with a  
• Fan Housing  
3
/
5
/
7
/
23 ga. Galvanized metal housing, dimensions 7 8" x 7 8" x 5 8",  
double metal thickness mounting tabs.  
7
rough in opening of 75 8" x 7 8". The housing will mount through  
/
/
drywall thickness up to 3 4".  
/
• Duct Collar  
• Ventilating Area  
Plastic collar for 4" duct connection, comes complete with built  
in non-metallic back draft damper for quiet operation.  
For bathrooms up to 70 sq. ft. for other rooms up to 85 sq. ft.  
• Single Pack Shipping Info  
• Lighting  
3
1
3
/
/
/
Box Dim: 11 4" x 13 4" x 9 8"  
UPC: 0-8316227611-7  
100 watt maximum, type A19, medium base bulb.  
Shipping Weight: 6 lbs.  
PERFORMANCE  
HVI Sones Fan Speed Power  
Static Pressure (inches of w.g.)  
@ .1 SP  
RPM  
Watts  
0
77  
0.05  
73  
0.1  
70  
0.125  
69  
0.15  
68  
0.2  
66  
0.25  
64  
0.3  
62  
Air Flow - CFM  
4.0  
1725  
44  
PROJECT  
ARCHITECT  
ENGINEER  
LOCATION  
CONTRACTOR  
SUBMITTED BY  
DATE  
FAN  
MODEL  
IN  
W.G.  
OPTIONAL EQUIPMENT  
& REMARKS  
CFM  
RPM  
WATTS AMPS  
SONES  
QTY  
NUMBER NUMBER  
U.S.: 820 Lincoln Drive  
Canada: 110 Glidden Road  
Brampton, Ontario L6T 2J3  
Tel: (905) 456-2033  
West Chester, Pennsylvania 19380-4466  
Tel: (610) 692-7400 • 877-304-3785  
Fax: (610) 696-8048  
C
US  
Fax: (905) 456-1015  
Specifications subject to change without notice.  
Updated 5-06  
 

Abocom Network Card CFM560 User Manual
Adcom Stereo System GFR 700HD User Manual
Aiphone CRT Television KC 32EU User Manual
AKG Acoustics Microphone C 414B TLII User Manual
Alto Shaam Food Warmer ED2SYS 48 2S User Manual
American Aldes Ventilation Hood RDF 8 8IP User Manual
American Standard Indoor Furnishings 0293004 User Manual
ATON Stereo Receiver HDR44 User Manual
Avocent Switch CPS1610 User Manual
Beckett Water Gardening Outdoor Fountain 1409 User Manual