Carrier Heat Pump 50JZ A User Manual

50JZ---A  
Single Packaged Heat Pump System  
With Puron (R---410A) Refrigerant  
50Hz, CE  
7 --- 14k W ( Si ze s 24 --- 48)  
Owner’s Information Manual  
A09042  
Fig. 1 - Unit 50JZ-A  
NOTE TO EQUIPMENT OWNER:  
For your convenience, please record the model and serial numbers of your new equipment in the spaces  
provided. This information, along with the installation data and dealer contact information, will be helpful  
should your system require maintenance or service.  
UNIT INFORMATION  
INSTALLATION INFORMATION  
Model # _____________________________________  
Serial # ______________________________________  
Date Installed ________________________________  
DEALERSHIP CONTACT INFORMATION  
Company Name_______________________________  
Address______________________________________  
_____________________________________________  
Phone Number _______________________________  
Technician Name _____________________________  
_____________________________________________  
ACCESSORIES (List type and model #)  
_____________________________________________  
_____________________________________________  
_____________________________________________  
NOTE TO INSTALLER:  
This manual must be left with the equipment owner.  
1
 
sorbed from the outside air. So, to maintain energy--efficient opera-  
tion, your unit has an automatic defrost mode.  
instance of filter grilles, the filters can simply be removed from the  
grille and replaced.  
The other typical application is an accessory filter rack installed in-  
side the unit itself. The following information is given to assist in  
changing filters used in these internal filter racks.  
The defrost mode starts at a preset time interval of 60 minutes, al-  
though, it may be reset to 30, 90 or 120 minutes. Defrost will start  
at the preset time only if the ice is sufficient to interfere with normal  
heating operation.  
Table 1 indicates the correct indoor filter size for your unit. Refer  
to Fig.2 to access filters installed in the accessory filterrack. Ifusing  
an Accessory Filter Rack, refer to the Installation Instructions pro-  
vided with it for correct filter sizes and quantities.  
After the ice is melted from the coil, or after a maximum of 10 min-  
utes in defrost mode, the unit automatically switches back to normal  
heating operation.  
Table 1—Air Filters Located Inside Unit  
(For Replacement Purposes)  
Do not be alarmed if steam or fog appears at the outdoor unit during  
defrost mode. Water vapor from the melting ice may condense into  
a mist in the cold outside air.  
Unit Size  
A24  
Filter Size in. (mm)  
20x20x1 (508x508x25)  
20x24x1 (508x610x25)  
24x30x1 (610x762x25)  
24x36x1 (610x914x25)  
During certain weather conditions such as heavy snow and freezing  
rain it is not uncommon for ice to build up on the unit grille. This is  
normal for these weather conditions. Do not attempt to remove the  
ice from the unit grille. This condition will not affect the proper  
function of the unit and will clear within a few days.  
A30  
A36  
A48  
Emergency Heating Mode  
To replace or inspect filters in accessory filter rack:  
In the event of primary unit heat failure, the emergency heat mode  
allows your supplemental heating source to keep your home or of-  
fice warm until your unit can be serviced. Contact your dealer in the  
event of primary unit heat failure.  
1. Remove the filter access panel (See Fig.2) using a 5/16--in.  
nut driver.  
2. Removethefilter(s)by pulling itoutoftheunit.If thefilter(s)  
is dirty, clean or replace with a new one.  
MAINTENANCE AND SERVICE  
When installing the new filter(s), note thedirection ofthe airflow ar-  
rows on the filter frame.  
This section discusses maintenance that should be performed by  
your dealer and care you, as the owner, may wish to handle for your  
new unit.  
If you have difficulty locating your air filter(s) or have questions  
concerning proper filter maintenance, contact your dealer for in-  
structions. When replacing filters, always use the same size and type  
of filter that was supplied originally by the installer.  
Routine Maintenance  
All routine maintenance should be handled by skilled, experienced  
personnel. Your dealer can help you establish a standard procedure.  
To assure proper functioning of the unit, flow of condenser air must  
not be obstructed from reaching the unit. Clearance from the top of  
the unit is 48 in. (1219 mm). Clearance of at least 36 in. (914 mm)  
is required on sides except the power entry side (42 in. clearance)  
(1067 mm) and the duct side (12 in. minimum clearance) (305mm).  
Maintenance and Care for the Equipment Owner  
Before proceeding with those things you might want to maintain  
yourself, please carefully consider the following:  
!
WARNING  
FIRE, EXPLOSION, ELECTRICAL SHOCK, CUT  
HAZARD  
Filter Access  
Panel For  
Accessory Filter  
Rach  
Failure to follow this warning could result in personal injury,  
death or property damage.  
Access Panels  
1. TURN OFF ELECTRICAL POWER TO YOUR UNIT  
BEFORE  
SERVICING  
OR  
PERFORMING  
A09380  
MAINTENANCE AND INSTALL A LOCK--OUT TAG.  
Fig. 2 - Accessory Filter Rack Access Panel  
2. When removing access panels or performing maintenance  
functions inside your unit, be aware of sharp sheet metal  
parts and screws. Although special care is taken to reduce  
sharp edges to a minimum, be extremely careful when  
handling parts or reaching into the unit.  
!
WARNING  
FIRE AND UNIT OPERATION HAZARD  
Failure to follow this warning could result in personal injury,  
death or property damage.  
Air Filters  
The air filter(s) should be checked every 3 or 4 weeks and changed  
or cleaned whenever it becomes dirty. Dirty filters produce exces-  
sive stress on the blower motor and can cause the motor to overheat  
and shut down.  
Never operate your unit without filters in place. An  
accumulation of dust and lint on internal parts of your unit can  
cause loss of efficiency.  
Fans and Fan Motor  
This unit must have an air filter in place before it can be operated.  
These filters should be located in at least one of two places. In many  
applications, the installer will provide return air filter grilles  
mounted on the wall or ceiling of the conditioned structure. In the  
Periodically check the condition of fan wheels and housings and  
fan--motorshaftbearings.Contactyourdealerforthe requiredannu-  
al maintenance.  
3
 
Indoor and Outdoor Coils  
Regular Dealer Maintenance  
In addition to the type of routine maintenance you might be willing  
to perform, your unit should be inspected regularly by a properly  
trained service technician. An inspection (preferably each year, but  
at least every other year) should include the following:  
Cleaning of the coils should only be done by qualified service per-  
sonnel. Contact your dealer for the required annual maintenance.  
Condensate Drain  
The drain pan and condensate drain line should be checked and  
cleaned at the same time the cooling coils are checked by your deal-  
er.  
1. Inspection and, if required, cleaning of the outdoor and  
indoor coils.  
2. Inspection and, if required, cleaning of the indoor coil drain  
pan.  
Compressor  
3. Inspection and cleaning of blower wheelhousing andmotor.  
All compressors arefactory shippedwith anormal chargeof thecor-  
rect type and quantity of refrigeration grade oil. A compressor  
should rarely require additional oil.  
4. Inspection of all supply and return air ducts for leaks,  
obstructions, and insulation integrity. Any problems found  
should be resolved at this time.  
Condenser Fan  
5. Inspectionof theunit baseto ensurethat nocracks, gaps,etc.,  
exist which may cause a hazardous condition.  
!
WARNING  
6. Inspection of the unit casing for signs of deterioration.  
7. Inspection of all electrical wiring and components to assure  
proper connection.  
PERSONAL INJURY AND UNIT DAMAGE HAZARD  
Failure to follow this warning could result in personal injury,  
death or property damage.  
8. Inspection for leaks in the refrigerant circuit. Pressure and  
temperature check to determine appropriate refrigerant  
charge.  
Do not poke sticks, screwdrivers, or any other object into  
revolving fan blades.  
9. Operational check of the unit to determine working  
conditions.Repairoradjustmentshouldbe madeat thistime.  
The fan must be kept free of all obstructions to ensure proper cool-  
ing. Contact your dealer for any required service.  
Your servicing dealer may offer an economical service contract that  
covers seasonal inspections. Ask for further details.  
Electrical Controls and Wiring  
Complete service instructions can be found in the unit Installation,  
Start--up and Service Instructions.  
Electrical controlsare difficultto checkwithout properinstrumenta-  
tion. If there are any discrepancies in the operating cycle, contact  
your local dealer and request service.  
Before you call for service...  
...check for several easily solved problems.  
If insufficient heating or cooling is suspected:  
Refrigerant Circuit  
Therefrigerantcircuitisdifficulttocheckforleakswithout theprop-  
er equipment. If inadequate cooling is suspected, contact your local  
dealer for service.  
( ) Check for sufficient airflow. Check the air filter for dirt. Check  
forblockedreturnor supplyair grilles. Be surethey areopen and un-  
obstructed. If these checks do not reveal the cause, call your servic-  
ing dealer.  
!
WARNING  
If your unit is not operating at all, check the following list for  
easy solutions:  
EXPLOSION, BURN AND ENVIRONMENTAL  
HAZARD  
( ) Check to be sure that your thermostat temperature selector is set  
below the indoor temperature during the cooling season or above  
theindoortemperatureduring heatingseason. Besure theSYSTEM  
switch or MODE control is in the COOL or HEAT and not OFF.  
Failure to follow this warning could result in personal injury,  
death or property damage.  
System under pressure. Relieve pressure and recover all  
refrigerant before system repair or final unit disposal. Use all  
service ports and open all flow--control devices, including  
solenoid valves.  
(
) If your unit still fails to operate, call your servicing dealer for  
troubleshooting and repairs. Specify the model and serial numbers  
of your unit. (Record them in this manual in the space provided.) If  
the dealer knows exactly which unit you have, he may be able to of-  
fer suggestions over the phone, or save valuable time through  
knowledgeable preparation for the service call.  
Unit Panels  
After performing any maintenance or service on the unit, be sure all  
panels are fastened securely in place to prevent rain from entering  
unit cabinet and to prevent disruption of the correct unit airflow pat-  
tern.  
In Case of Trouble  
If you perform the steps above and unit performance is still unsatis-  
factory, shut off the unit and call your dealer.  
HEATING & COOLING  
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under the  
“Heating Equipment” or “Air Conditioning Contractors & Systems” heading for dealer listing by brand name.  
Have available the Model No., Series Letter, & Serial No. of your equipment to ensure correct replacement part.  
Copyright 2009 Carrier Corporation  
Printed in the U.S.A.  
Edition Date: 06/09  
Catalog No: OM50JZ---C01  
Manufacturer reserves the right to change, at any time, specifications and design without notice and without obligation.  
Repl a ce s: OM 5 0 --- C 2  
4
 

Best Ventilation Hood WPD28I User Manual
Black Decker Food Processor FP1611SCKT User Manual
Blomberg Washer WNF 9402 C20 User Manual
Bryant Furnace 355M 40 4 User Manual
Canon All in One Printer 4498B030 User Manual
Canon Scanner 3297B002 User Manual
Canon Scanner CS S 43 User Manual
Carrier Air Conditioner 38AH044 084 User Manual
Casio Tablet IT 300 User Manual
Chamberlain Garage Door Opener WD962KEV User Manual