Fyrnetics Smoke Alarm PE120 User Manual

PHOTOELECTRIC SMOKE AND FIRE ALARM  
USER’S GUIDE  
MODEL PE120  
A.C. Wire-in Single and/or Multiple Station (24 units maximum)  
Photoelectric Smoke Alarm with 9 Volt Battery Back Up  
Thank you for purchasing this Fyrnetics smoke and fire alarm. It is an  
important part of your family’s home safety plan. You can trust  
Fyrnetics to provide the highest quality safety products. We know you  
expect nothing less when the lives of your family are at stake.  
For your convenience, write down the following information.  
If you call our Consumer Hotline, these are the first questions  
you will be asked.  
Smoke Alarm Model Number (located on back of detector):  
Date Code (located on back of detector). Manufacturer recommends  
replacing this alarm ten years from the date code:  
Date of Purchase:  
Where Purchased:  
LISTED  
 
WARNING! REMOVAL OF THE SMOKE ALARM BATTERY AND DISCONNECTING OR LOSS  
OF A.C. POWER WILL RENDER THE SMOKE ALARM INOPERATIVE.  
SINGLE FLOOR PLAN  
ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per detector (maximum 80mA for originat-  
ing unit with 24 alarms interconnected).  
IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND KEEP THIS MANUAL  
NEAR THE ALARM FOR FUTURE REFERENCE.  
CONTENTS OF THIS MANUAL  
MULTIPLE FLOOR PLAN  
1 -- RECOMMENDED LOCATIONS FOR SMOKE ALARMS  
2 -- LOCATIONS TO AVOID  
3 -- INSTALLATION INSTRUCTIONS  
4 -- OPERATION AND TESTING  
5 -- NUISANCE ALARMS  
6 -- MAINTENANCE  
7 -- LIMITATIONS OF SMOKE ALARMS  
8 -- GOOD SAFETY HABITS  
DIAGRAM A  
9 -- NFPA PROTECTION STANDARD 72, SECTION 2-2.1  
10 -- SERVICE AND WARRANTY  
Smoke Alarms for Minimum Protection  
Smoke Alarms for Maximum Protection  
Smoke Alarms with “HUSH” Control  
Do not try to repair the smoke alarm yourself. Refer to the instructions in Section 11 for service.  
DIAGRAM B  
1. RECOMMENDED LOCATIONS FOR DETECTORS  
Locate the first alarm in the immediate area of the bedrooms. Try to protect the exit path as the  
bedrooms are usually farthest from the exit. If more than one sleeping area exists, locate addi-  
tional alarms in each sleeping area.  
MOBILE HOME INSTALLATION  
Mobile homes built in the past five to seven years have been designed to be energy efficient.  
Install smoke alarms as recommended above (refer to RECOMMENDED LOCATIONS and Diagram  
A).  
Locate additional alarms to protect any stairway as stairways act like chimneys for smoke and  
heat.  
Locate at least one alarm on every floor level.  
In mobile homes that are not well insulated compared to present standards, extreme heat or cold  
can be transferred from the outside to the inside through poorly insulated walls and roof. This may  
create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceil-  
ing. In such units, install the smoke alarm on an inside wall with the top edge of the alarm at a  
minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see Diagram A).  
Locate an alarm in every bedroom where a smoker sleeps.  
Locate an alarm in every room where electrical appliances are operated (i.e. portable heaters or  
humidifiers).  
Locate an alarm in every room where someone sleeps with the door closed. The closed door  
may prevent the alarm from waking the sleeper.  
If you are not sure about the insulation in your mobile home, or if you notice that the outer walls  
and ceiling are either hot or cold, install the alarm on an inside wall. For minimum protection,  
install at least one alarm close to the bedrooms. For additional protection, see SINGLE FLOOR  
PLAN in Diagram B.  
Smoke, heat, and combustion products rise to the ceiling and spread horizontally. Mounting the  
smoke alarm on the ceiling in the center of the room places it closest to all points in the room.  
Ceiling mounting is preferred in ordinary residential construction.  
WARNING:TEST YOUR SMOKE ALARM OPERATION AFTER R.V. OR MOBILE HOME VEHICLE  
HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE.  
For mobile home installation, select locations carefully to avoid thermal barriers that may form at  
the ceiling. For more details, see MOBILE HOME INSTALLATION below.  
When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm) from the side wall  
and 2 feet (60.96 cm) from any inside corner (see Diagram A).  
When mounting the alarm on the wall, it is best to use an inside wall with the top edge of the  
alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling, and at  
least 2 feet (61 cm) from any inside corner (see Diagram A).  
Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or room is  
more than 30 feet (9.1 m) long.  
 
2. LOCATIONS TO AVOID  
Alarms must not be located within 3 feet of the following:  
Supply and return registers used for forced air heating and air conditioning.  
Ceiling fans and other high air flow areas.  
Bathrooms which contain a tub or shower.  
In general, alarms should not be located:  
In the garage. Products of combustion are present when you start your automobile.  
In an area where the temperature may fall below 40ºF or rise above 100ºF.  
In dusty areas. Dust particles may cause nuisance alarms or failure to alarm.  
In very humid areas or near a bathroom. Moisture or steam can cause nuisance alarms.  
Near fluorescent lights. Electronic “noise” may cause nuisance alarms.  
Optional Accessory  
FIGURE 1 INTERCONNECT WIRING DIAGRAM  
3. INSTALLATION INSTRUCTIONS  
WIRING REQUIREMENTS  
WIRES ON DETECTOR HARNESS  
CONNECTED TO  
Black  
White  
Red  
Hot Side of A.C. Line  
This smoke alarm should be installed on a U.L. listed or recognized junction box. All connec-  
tions should be made by a qualified electrician and must conform to article 760 of the U.S.  
National Electrical Code, NFPA 72 and/or any other codes having jurisdiction in your area.  
Neutral Side of A.C. Line  
Interconnect Lines (Red Wires) of Other  
Units in the Multiple Station Set up  
The appropriate power source is 120 Volt A.C. Single Phase supplied from a non-switchable cir-  
cuit which is not protected by a ground fault interrupter.  
BATTERY INSTALLATION  
See MAINTENANCE (Section 6) for battery installation.  
WIRING INSTRUCTIONS FOR A.C. QUICK CONNECT HARNESS  
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY  
COMPARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE A.C. QUICK  
CONNECTOR WILL NOT ATTACH TO THE DETECTOR, AND THE DETECTOR WILL NOT ATTACH  
TO THE TRIM RING (SEE SECTION 6, FIGURE 6).  
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.  
For units that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING.  
Leave the red wire insulating cap in place to make certain that the red wire cannot contact any  
metal parts or the electrical box.  
MOUNTING INSTRUCTIONS  
CAUTION:THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!  
When alarms are interconnected, all interconnected units must be powered from a single circuit.  
A maximum of 24 Lifesaver devices may be interconnected in a multiple station arrangement.  
The interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms  
and/or 18 alarms total (smoke, heat, carbon monoxide, etc.) With 18 alarms interconnected, it is  
still possible to interconnect up to a total of 6 remote signaling devices and/or relay modules.  
1. Remove the trim ring from the back of the alarm by holding the trim ring and twisting the alarm  
in the direction indicated by the “OFF” arrow on the alarm cover.  
2. After selecting the proper smoke alarm location as described in Section 1 and wiring the A.C.  
QUICK CONNECT harness as described in the WIRING INSTRUCTIONS, attach the trim ring to  
the electrical box (see Figure 2).  
3. Use a screwdriver to punch out only the pair of holes in the trim ring that match your type of  
electrical box or plaster ring. Mount the trim ring to the electrical box, using the appropriate  
holes. NOTE: Use the circle, square and octagon markings near each mounting hole in the trim  
ring to help you select the correct mounting holes (see Figure 2).  
4. Pull the A.C. QUICK CONNECTOR through the center hole in the trim ring and mount the ring,  
making sure that the mounting screws are positioned in the small ends of the keyholes before  
tightening the screws (see Figure 2).  
When mixing models which have battery backup (1275, 1275H, 1285, HD135F) with models  
without battery backup (1235, 120X, SL177i, FYCO 31) be advised that the models without bat-  
tery backup will not respond during an AC power failure.  
The maximum wire run distance between the first and last unit in an interconnected system is  
1000 feet.  
Figure 1 illustrates interconnection wiring. Improper connection will result in damage to the  
alarm, failure to operate, or a shock hazard.  
Make certain alarms are wired to a continuous (non-switched) power line. NOTE: Use standard  
UL listed household wire (18 gauge or larger as required by local codes) available at all electri-  
cal supply stores and most hardware stores.  
5. Plug the A.C. QUICK CONNECTOR into the back of the alarm (see Figure 3), making sure that  
the locks on the connector snap into place. Then push the excess wire back into the electrical  
box through the hole in the center of the trim ring.  
6. If you have finished all the WIRING, BATTERY INSTALLATION AND TRIM RING MOUNTING  
STEPS, you can install the alarm on the trim ring. Alignment marks are provided on the side of  
the alarm and on the trim ring (see Figure 4).  
7. Install the alarm on the trim ring with the indicating marks aligned and rotate the alarm in the  
direction of the “ON” arrow on the cover until the alarm snaps in place (see Figure 4).  
 
8. Turn on the A.C. power. The green A.C. Power On Indicator should be lit when the alarm is  
operating from A.C. power.  
FIGURE 2. SELECT CORRECT MOUNTING HOLES ON TRIM RING  
FLASHING LED LIGHT: This smoke alarm is equipped with a flashing red indicator LED. The LED  
is located under the test button and has three modes of operation.  
Standby Condition  
Alarm Condition  
The red LED will flash every 30-40 seconds to indicate that the smoke  
alarm is operating properly.  
When the alarm senses products of combustion and goes into alarm,  
the red LED will flash rapidly (2-3 times per second). The rapid flashing  
LED and pulsating alarm will continue until the air is cleared.  
Low Battery Condition The LED flash will be accompanied by an audible chirp. Replace the  
battery when this condition occurs.  
SMOKE SENSING CHAMBER OPERATION: This alarm will “chirp” if any of the components in the  
smoke sensing chamber fail. This chirp will occur between the flashes of the red LED indicator  
light. (If the chirp occurs at the same time as the red LED flash, see Section 6 for low battery infor-  
mation.)  
Rectangular Plaster Ring  
Circular Plaster Ring  
Octagonal Electrical Box  
WHEN UNITS ARE INTERCONNECTED, only the red LED of the unit which senses the smoke or is  
being tested (the originating unit) will flash rapidly. All other units in the interconnect system will  
sound an alarm but their red LED’s will NOT flash rapidly.  
TAMPER RESIST LOCKING PIN: To make your smoke alarm somewhat tamper resistant, a locking  
pin has been provided with your alarm. Using this pin will deter children and others from removing  
the alarm from trim ring. To use the pin, insert it into the hole in the side of the alarm after the  
alarm has been installed on the trim ring (see Figure 5)  
TESTING: Test by pushing the test button on the cover and hold it down for a minimum of 5 sec-  
onds. This will sound the alarm if all the electronic circuitry, horn and battery are working. If no  
alarm sounds, check the fuse or circuit breaker supplying power to the alarm circuit. If the alarm  
still does not sound, the unit has defective batteries or other failure. You can also test the alarm by  
blowing smoke into it.  
Alignment  
To remove A.C.  
marks  
connector,  
squeeze  
locking arms  
and pull  
Tamper resistant  
locking pin  
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION. Erratic or low sound coming from  
your alarm may indicate a defective alarm, and it should be returned for service (see Section 11).  
5. NUISANCE ALARMS  
Smoke alarms are designed to minimize nuisance alarms. Cigarette smoke will not normally set off  
the alarm, unless the smoke is blown directly into the alarm. Combustion particles from cooking  
may set off the alarm if the alarm is located close to the cooking area. Large quantities of com-  
bustible particles are generated from spills or when broiling. Using the fan on a range hood which  
vents to the outside (non-recirculating type) will also help remove these combustible products from  
the kitchen.  
Install  
Remove  
FIGURE 3  
FIGURE 4  
FIGURE 5  
NOTE the tamper resist pin will have to be removed in order to change the batteries. Use a long  
nose pliers to pull the pin out of the hole. It is now possible to remove the detector from the trim  
ring.  
If the alarm does sound, check for fires first. If a fire is discovered, get out and call the fire depart-  
ment. If no fire is present, check to see if one of the reasons listed in Section 2 may have caused  
the alarm.  
After installation, TEST your alarm by pressing and holding the test button for several seconds, or  
by blowing smoke into the alarm. This should sound the alarm.  
CAUTION! Early warning fire detection is best achieved by the installation of fire detection equip-  
ment in all rooms and areas of the household as follows: A smoke alarm installed in each separate  
sleeping area (in the vicinity of - but outside of the bedroom), and heat or smoke alarms in the liv-  
ing room, dining room, kitchen, hallways, attic, furnace room, closets, utility storage room, base-  
ment, and attached garage.  
6. MAINTENANCE  
ALARM REMOVAL  
IF TAMPER RESIST PIN HAS BEEN USED, REFER TO TAMPER RESIST LOCKING PIN IN  
SECTION 3 FOR PIN REMOVAL INSTRUCTIONS.  
4. OPERATION AND TESTING  
OPERATION: The smoke alarm is operating once A.C. power is applied, fresh batteries are  
installed and testing is complete. When the smoke alarm’s photoelectric chamber senses products  
of combustion, the horn will sound a loud (85db) pulsing alarm until the sensing chamber is  
cleared of smoke particles.  
 
To replace the battery, remove the alarm from the trim ring by rotating the alarm in the direction of  
the “OFF” arrow on the cover (see Section 3, Figure 4) To discon-  
nect the A.C. power harness, squeeze the locking arms on the  
sides of the Quick Connector while pulling the connector away  
from the bottom of the alarm (see Section 3, Figure 3).  
Smoke alarms are devices that can provide early warning of possible fires at a reasonable cost;  
however, alarms have sensing limitations. Ionization type alarms offer a broad range of fire  
sensing capabilities but are better at detecting fast flaming fires than slow smoldering fires.  
Photoelectric alarms sense smoldering fires better than flaming fires. Home fires develop in dif-  
ferent ways and are often unpredictable. Neither type of alarm (photoelectric or ionization) is  
always best, and a given alarm may not always provide warning of a fire.  
BATTERY INSTALLATION AND REMOVAL  
A battery powered alarm must have a battery of the specified type, in good condition and  
installed properly.  
To replace or install the batteries you must first remove the alarm  
from the trim ring by following the ALARM REMOVAL instructions at  
the beginning of this section. After alarm has been removed , you  
can open the battery door and install or replace the battery.  
Battery installation instructions are provided on the inside of the  
A.C. powered alarms will not operate if the A.C. power has been cut off, such as by an electrical  
fire or an open fuse.  
Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are in  
good operating condition.  
FIGURE 6  
battery door.  
Smoke alarms cannot provide an alarm if smoke does not reach the alarm. Therefore, smoke  
alarms may not sense fires starting in chimneys, walls, on roofs, on the other side of a closed  
door or on a different floor.  
When installing the battery, press the battery reminder finger down into the battery compartment  
and install the battery (see Figure 6).  
If the alarm is located outside the bedroom or on a different floor, it may not wake up a sound  
sleeper.  
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COM-  
PARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE A.C. QUICK CON-  
NECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL  
NOT ATTACH TO THE TRIM RING.  
The use of alcohol or drugs may also impair one’s ability to hear the smoke alarm. For maxi-  
mum protection, a smoke alarm should be installed in each sleeping area on every level of a  
home.  
This smoke alarm uses a 9V carbon zinc back up battery (alkaline and lithium batteries may also  
be used). A fresh battery should last for one year under normal operating conditions.  
Although smoke alarms can help save lives by providing an early warning of a fire, they are not  
a substitute for an insurance policy. Home owners and renters should have adequate insurance  
to protect their lives and property.  
This alarm has a low/missing battery monitor circuit which will cause the alarm to “chirp” approxi-  
mately every 30-40 seconds for a minimum of seven (7) days when the battery gets low. Replace  
the battery when this condition occurs.  
8. GOOD SAFETY HABITS  
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM REPLACEMENT.  
DEVELOP AND PRACTICE A PLAN OF ESCAPE  
Carbon-zinc type  
Alkaline type  
Lithium type  
EVEREADY 216 OR 1222; GOLD PEAK 1604P OR 1604S  
EVEREADY 522; DURACELL MN1604; GOLD PEAK 1604A; MX1604  
ULTRALIFE U9VL  
Make a floor plan indicating all doors and windows and at least two (2) escape routes from each  
room. Second story windows may need a rope or chain ladder.  
Have a family meeting and discuss your escape plan, showing everyone what to do in case of  
fire.  
NOTE: REGULAR TESTING IS RECOMMENDED!  
Determine a place outside your home where you all can meet if a fire occurs.  
WARNING! BE SURE TO FOLLOW BATTERY INSTALLATION INSTRUCTIONS PRINTED ON THE  
INSIDE OF THE BATTERY DOOR AND USE ONLY THE BATTERIES SPECIFIED. USE OF DIFFER-  
ENT BATTERIES MAY HAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM.  
Familiarize everyone with the sound of the smoke alarm and train them to leave your home when  
they hear it.  
Practice a fire drill at least every six months. Practice allows you to test your plan before an  
emergency. You may not be able to reach your children. It is important they know what to do.  
CLEANING YOUR ALARM  
WHAT TO DO WHEN THE ALARM SOUNDS  
To clean your alarm, remove it from the mounting bracket as outlined in the beginning of this sec-  
tion. You can clean your alarm by using compressed air or your vacuum cleaner hose to blow or  
suck air through the openings around the perimeter of the alarm. The outside of the alarm can be  
wiped with a damp cloth.  
Leave immediately by your escape plan. Every second counts, so don’t waste time getting  
dressed or picking up valuables.  
In leaving, don’t open any inside door without first feeling its surface. If hot, or if you see smoke  
seeping through cracks, don’t open that door! Instead, use your alternate exit. If the inside of  
the door is cool, place your shoulder against it, open it slightly and be ready to slam it shut if  
heat and smoke rush in.  
After cleaning, reinstall your alarm. Test your alarm by using the test button and check that the  
green LED is on.  
Stay close to the floor if the air is smoky. Breathe shallowly through a cloth, wet if possible.  
Once outside, go to your selected meeting place and make sure everyone is there.  
Call the fire department from your neighbor’s home - not from yours!  
7. LIMITATIONS OF SMOKE ALARMS  
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY  
 
Don’t return to your home until the fire officials say that it is all right to do so.  
FIVE YEAR LIMITED WARRANTY  
There are situations where a smoke alarm may not be effective to protect against fire as stated in the  
NFPA Standard 72. For instance:  
Fyrnetics warrants to the original purchaser that the enclosed smoke alarm (but not the bat-  
tery) will be free from defects in material and workmanship or design under normal use and  
service for a period of five years from the date of purchase. The obligation of Fyrnetics under  
this warranty is limited to repairing or replacing the smoke alarm or any part which we find to  
be defective in material, workmanship or design, free of charge to the customer, upon send-  
ing the smoke alarm with proof of date of purchase, postage and return postage prepaid, to  
Warranty Service Department, Fyrnetics 1394 South Third St., Mebane, N.C. 27302.  
a) smoking in bed  
b) leaving children home alone  
c) cleaning with flammable liquids, such as gasoline  
Further information on fire safety can be obtained in a pamphlet titled “IN A FIRE SECONDS  
COUNT” published by the NFPA, Batterymarch Park, Quincy, MA 02269  
This warranty shall not apply to the smoke alarm if it has been damaged, modified, abused or  
altered after the date of purchase or if it fails to operate due to improper maintenance or inad-  
equate A.C. or D.C. electrical power.  
9. NFPA REQUIRED PROTECTION  
THE LIABILITY OF FYRNETICS OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS  
ARISING FROM THE SALE OF THIS SMOKE ALARM OR UNDER THE TERMS OF THIS LIMIT-  
ED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF  
SMOKE ALARM AND, IN NO CASE, SHALL FYRNETICS, INC. OR ANY OF ITS PARENT OR  
SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES  
RESULTING FROM THE FAILURE OF THE SMOKE ALARM OR FOR BREACH OF THIS OR  
ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS  
CAUSED BY THE COMPANY’S NEGLIGENCE OR FAULT.  
The National Fire Protection Association’s Standard 72 reads as follows:  
2-2.1.1.1 Smoke alarms shall be installed outside each separate sleeping area in the immediate  
vicinity of the bedrooms and on each additional story of the family living unit, including basements  
and excluding crawl spaces and unfinished attics. In new construction, a smoke alarm shall be  
installed in each sleeping room.  
A-2.5.2.1 Smoke Detection - Are More Smoke Detectors Desirable? The required number of smoke  
alarms might not provide reliable early warning protection for those areas separated by a door  
from the areas protected by the required smoke alarms. For this reason, it is recommended that  
the householder consider the use of additional smoke alarms for those areas for increased protec-  
tion. The additional areas include the basement, bedrooms, dining room, furnace room, utility  
room, and hallways not protected by the required smoke alarms. The installation of the smoke  
alarms in the kitchen, attic (finished or unfinished), or garage is normally not recommended, as  
these locations occasionally experience conditions that can result in improper operation.  
Since some states do not allow limitations on the duration of an implied warranty or do not  
allow the exclusion or limitation of incidental or consequential damages, the above limitations  
or exclusions may not apply to you. While this warranty gives you specific legal rights, you  
may also have other rights which vary from state to state.  
Also, Fyrnetics makes no warranty, express or implied, written or oral, including that of  
merchantability or fitness for any particular purpose, with respect to the battery.  
This equipment should be installed in accordance with the National Fire Protection Association’s  
Standard 72 (NFPA, Batterymarch Park, Quincy, MA 02269).  
The above warranty may not be altered except in writing signed by both parties hereto.  
NOTIFY YOUR LOCAL FIRE DEPARTMENT AND INSURANCE COMPANY OF YOUR SMOKE  
ALARM INSTALLATION.  
10. SERVICE AND WARRANTY  
If after reviewing this manual you feel that your smoke alarm is defective in any way, do not tamper  
with the unit. Return it for servicing to: Fyrnetics 1394 South Third St., Mebane, N.C. 27302. (See  
Warranty for in-warranty returns)  
FYRNETICS  
1394 South Third St., Mebane, N.C. 27302.  
1-800-880-6788  
1375-7201-02  
 

Elation Professional Indoor Furnishings CMY Zoom 575 User Manual
Electro Voice Range P3000RL User Manual
Electro Voice Speaker System Eliminator ii User Manual
Fisher Price Baby Accessories T4841 User Manual
FMI Indoor Fireplace CGCFTNA User Manual
Freecom Technologies Computer Drive Desktop Hard Drives User Manual
Fujitsu Air Conditioner AOU18RC User Manual
Fujitsu Laptop S6120 User Manual
Fujitsu Power Supply FTR G1 User Manual
Goodman Mfg Digital Camera G SHOT 3029TFT User Manual