GENERAC® GUARDIAN® SERIES
STANDBY GENERATORS
8 kW - 10 kW - 14 kW
Air-Cooled Gas Engine Generator Sets
Includes:
Standby Power Rating
Model 005882-1 (Steel - Bisque) - 8 kW 60Hz
Model 005883-1 (Steel - Bisque) - 10 kW 60Hz
Model 005884-1 (Steel - Bisque) - 14 kW 60Hz
®
• True Power Electrical Technology
• Two Line LCD Tri-lingual
Digital Nexus™ Controller
• Electronic Governor
• External Main Circuit Breaker,
System Status & Maintenance
Interval LED Indicators
• Sound Attenuated Enclosure
• Flexible Fuel Line Connector
• Composite Mounting Pad
• Natural Gas or LP Gas Operation
• 3 Year Limited Warranty
• UL 2200 Listed
FEATURES
¡
INNOVATIVE DESIGN & PROTOTYPE TESTING are key components
of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it
doesn’t stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
¡
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY
by electronically torque-matching the surge loads to the engine. An
unequalled ±1% voltage regulation.
¡
¡
TRUE POWER® ELECTRICAL TECHNOLOGY: Superior harmonics and
sine wave form produce less than 5% Total Harmonic Distortion for utility
quality power. This allows confident operation of sensitive electronic equipment
and micro-chip based appliances, such as variable speed HVAC.
¡
¡
SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
TEST CRITERIA:
GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
PROTOTYPE TESTED
SYSTEM TORSIONAL TESTED
NEMA MG1-22 EVALUATION
MOTOR STARTING ABILITY
®
SPECIFICATIONS
GENERATOR
Model 005882-1 (8 kW) Model 005883-1 (10 kW) Model 005884-1 (14 kW)
Rated Maximum Continuous Power Capacity (LP)
Rated Maximum Continuous Power Capacity (NG)
Rated Voltage
8,000 Watts*
7,000 Watts*
10,000 Watts*
9,000 Watts*
14,000 Watts*
13,000 Watts*
240
240
240
Rated Maximum Continuous Load Current – 240 Volts
Total Harmonic Distortion
33.3 LP/29.2 NG
Less than 5%
41.6 LP/37.5 NG
Less than 5%
58.3 LP/54.2 NG
Less than 5%
Main Line Circuit Breaker
35 Amp
45 Amp
60 Amp
Phase
1
1
1
Number of Rotor Poles
2
2
2
Rated AC Frequency
60Hz
60Hz
60Hz
Power Factor
1
1
1
Battery Requirement (not included)
Group 26R 12 Volts and 525
Group 26R 12 Volts and 525
Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum Cold-cranking Amperes Minimum Cold-cranking Amperes Minimum
Unit Weight (Pounds/Kilos)
340/154.2
387/175.4
439/199.1
Dimensions (L x W x H) Inches/mm
Sound output in dB(A) at 23 ft. with generator operating at normal load
48 x 25 x 29 (1218 x 638 x 732)
63
62
66
ENGINE
Model 005882-1 (8 kW) Model 005883-1 (10 kW) Model 005884-1 (14 kW)
Type of Engine
GENERAC OHVI
GENERAC OHVI V-TWIN
GENERAC OHVI V-TWIN
Number of Cylinders
Displacement
1
410cc
2
530cc
2
992cc
Cylinder Block
Aluminum w/Cast Iron Sleeve
Overhead Valve
Solid-state w/Magneto
Electronic
Aluminum w/Cast Iron Sleeve
Overhead Valve
Solid-state w/Magneto
Electronic
Aluminum w/Cast Iron Sleeve
Overhead Valve
Solid-state w/Magneto
Electronic
Valve Arrangement
Ignition System
Governor System
Compression Ratio
Starter
9.4:1
12 Vdc
9.5:1
12 Vdc
9.5:1
12 Vdc
Oil Capacity Including Filter
Operating RPM
Approx. 1.5 Qts./1.4L
3,600
Approx. 1.7 Qts./1.6L
3,600
Approx. 1.9 Qts./1.8L
3,600
Fuel Consumption
Natural Gas
cu.ft./hr.
1/2 Load
Full Load
77
102
156
139
156
220
3
Liquid Propane ft /hr (gal/hr) [Liter/hr]
1/2 Load
Full Load
34 (0.94) [3.56]
62 (1.68) [6.36]
46 (1.25) [4.73]
70 (1.93) [7.31]
58 (1.56) [5.91]
84 (2.30) [8.71]
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)
CONTROLS
2-Line Plain Text LCD Display (10 & 14 kW)
Mode Switch
Simple user interface for ease of operation.
-Auto
Automatic Start on Utility failure. 7 day exerciser.
-Off
Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start)
Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds
Engine Start Sequence
Standard
Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).
Engine Warm-up
5 seconds
Engine Cool-Down
1 minute
Starter Lock-out
Starter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery Charger
Standard
Standard
Standard
Standard, 72Hz
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection
Automatic Low Oil Pressure Shutdown
Overspeed Shutdown
High Temperature Shutdown
Overcrank Protection
Safety Fused
Failure to Transfer Protection
Low Battery Protection
50 Event Run Log
Future Set Capable Exerciser
Incorrect Wiring Protection
Internal Fault Protection
Common External Fault Capability
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).
Generac® Guardian® Series Guardian Standby Generator - 8 kW - 10 kW - 14 kW
AVAILABLE ACCESSORIES
Model #
Product
Discription
Every standby generator requires a battery to start the system. Generac offers the
recommended 26R wet cell battery for use with all air-cooled standby product.
5819
26R Wet Cell Battery
If the temperature regularly falls below 32° F, install a cold weather kit to maintain
optimal battery temperature. Kit consists of battery warmer with thermostat built
into the wrap.
5948 - 8 & 10kW
5947 - 14kW
Cold Weather Kit
Auxiliary Transfer Switch
Contact Kit
The auxiliary transfer switch contact kit allows the transfer switch to lock out a
single large electrical load you may not need.
5621
5703
Paint Kit
Bisque Kit
5662 - 8kW
5663 - 10kW
5664 - 14kW
Generac's scheduled maintenance kits provide all the hardware necessary to
perform complete routine maintenance on a Generac automatic standby generator.
Scheduled Maintenance Kit
Nexus Wireless Remote
Completely wireless and battery powered, Generac's Nexus wireless remote monitor
provides you with instant status information without ever leaving the house.
5928
5951
5937
Remotely control generator functions with the advanced model's LCD display. In
addition to remote testing of the generator, set the excercise cycle and maintenance
interval reminders.
Advanced Nexus Wireless
Remote
DLM Modules are used in conjunction with the Nexus Smart Switch to increase
its load management capabilities. It gives the Nexus Smart Switch additional load
management flexibility not found in any other transfer switch.
DLM Load Control DLM
Module (50 Amps)
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
637.6
[25.1]
1218
[47.9]
731.9
[28.8]
®
642
[25.3]
76.2 [3.0]
PEA GRAVEL
MINIMUM
1226
[48.3]
FRONT VIEW
LEFT SIDE VIEW
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186170SBY-G Printed in U.S.A. 07/11/12
|