Honeywell Dehumidifier DH90 User Manual

DH90 Whole House Dehumidifier  
with fresh air ventilation  
Installation Guide  
Dehumidification  
Fresh Air Ventilation  
Compact Size  
Energy Efficient  
The DH90 whole house dehumidifier integrates  
high-capacity dehumidification, fresh air ventila-  
tion, and filtration, into a compact and easy to  
install enclosure.  
Fresh Air Ventilation (optional)  
An automatic ventilation controller and dehumidi-  
stat are included.  
Fresh air may be ducted to the unit and regulated  
using the provided Honeywell W8150 fresh air  
ventilation controller along with the optional  
EARD6 damper.  
The dehumidifier removes 90 pints of water from  
the air per day (80F, 60% RH) while only using 6.2  
Amps of electricity.  
The high moisture removal capacity helps main-  
tain proper levels of humidity in most homes.  
Dehumidification  
The DH90's high efficiency refrigeration system is  
further enhanced with a heat exchanger to achieve  
exceptional performance while keeping your energy  
costs as low as possible.  
HVAC Installer: Please leave manual for homeowner.  
® U.S. Registered Trademark.  
Copyright © 2006 Honeywell International Inc.  
All rights reserved.  
69-1951  
 
For HVAC Installer Only • Installation Guide  
4.1A Power Accessibility  
1. Intended Application for DH90  
Unit should be located in an area where the cord’s  
length (10') should easily reach a 115 VAC electrical  
outlet with a minimum of a 15 A circuit capacity.  
The DH90 is intended for use in residential  
applications to reduce the indoor humidity levels  
and increase comfort. With the optional ventilation  
ducting and ventilation control hookup, the device  
also provides precise amounts of ventilation air.  
4.1B Accessibility  
The installed DH90 should have at least 14 inches  
of clearance in the front of the device to service  
the filter.  
2. Approvals  
The DH90 is certified by ETL to meet UL 474 and  
CSA 22.2 No. 92.  
4.1C Support Structure and Suspension  
Place the DH90 on supports to raise the base of the  
unit. Do not place the DH90 directly on structural  
building members without vibration absorbers or  
unwanted noise may result.  
3. Specifications  
Model: DH90  
Electrical: 110-120 VAC, 6.2 Amps,  
60 Hz, grounded  
The DH90 may be suspended from structural  
members by supporting the entire base of the unit  
via cross members, rigid frame, or the like. Do not  
hang the a DH90 from the cabinet. Remember to  
place a drain pan under the unit if it is suspended  
above a finished area or above an area where  
water leakage could cause damage.  
Capacity: 90 pints/day @ 80°F, 60%  
RH  
Inlet air temperature range: 55°F min., 100°F max.  
Air Flow: 200CFMwithoutexternal  
ducting  
4.1D Sizing Chart  
Refrigerant Charge: 1 lb., 12 oz. R22  
*This sizing chart is based on extreme climates where Rh levels  
are between 70 and 90% outdoor Rh. For less extreme climates  
then larger homes can be adequetely served. Actual requirements  
Duct Connections: Round 10" inlet, 10"  
outlet, 6" ventilation  
inlet  
may vary.  
Filter Size: Pleated MERV 11:  
14" x 14" x 1"  
Dehumidifier Capacity Required to  
Maintain Desired Indoor Rh*  
Unit Size (w/o Duct Collars): 34.5"L x 15.75"W  
x 20.875"H  
60% Indoor 55% Indoor 50% Indoor  
Home Size  
Rh  
Rh  
Rh  
(square  
feet)  
Unit Weight: 92 lbs  
Pints/day  
49-54  
Pints/day  
55-58  
Pints/day  
71-78  
Shipping Weight: 99 lbs  
2080  
2600  
3120  
61-68  
75-82  
65-72  
79-86  
90-97  
4. Installation  
95-110  
4.1 Installation Checklist  
4.2 Electrical Requirements  
ImPORTANT: Prior to installation of the  
DH90, the following checklist should be  
reviewed.  
WARNINg: Installation must be performed  
by a qualified service technician and must  
comply with local codes. Remove power to  
the device before installing or servicing the  
device. Failure to connect the device  
The DH90 can be installed in a variety of locations  
to meet the owner’s needs, and integrate with  
existing forced air systems or existing ductwork  
if desired. Choose a location with consideration  
to accessibility for service, drain availability, and  
power outlet location.  
according to these instructions may result in  
damage to the device or the controls.  
 
DH90 Dehumidifier • For HVAC Installer Only  
The DH90 plugs into a common grounded 115VAC  
outlet. The device draws 6.2 Amps under normal  
operating conditions. If used in an area which  
may become wet, a ground fault interrupter (GFI)  
protected circuit is recommended.  
4.4 Ducting  
ImPORTANT: When connecting ventilation  
duct, remove the label and 6" round  
insulation plug from the ventilation duct  
opening. If not using ventilation feature,  
leave the insulation intact.  
ImPORTANT: Do not install the humidistat  
where it may not accurately sense the relative  
humidity such as near HVAC supply registers,  
near exterior doors, on an outside wall, near a  
window, or near a water source.  
For the ideal installation, draw air from the central  
part of the home and return it to the isolated areas  
of the home like the bedrooms, den, utility room,  
or family room. See Fig. 1. Alternative installation  
option can be completed by drawing air directly  
from the return ducting and distributing through  
the supply air to the home.  
Refer to Section 6 for typical hookup diagrams.  
Some of the control wires leaving the DH90 may  
not be used with certain installations and should  
be left unconnected with wire nuts taped onto the  
stripped ends for safety.  
4.4A Fresh Air / Supply Air  
4.3 Condensate (Water) Removal  
ImPORTANT: DO NOT draw air directly from  
the kitchen, laundry, or isolated basement.  
The DH90 removes a large amount of moisture  
from the air and the device must be connected to  
a drain line that will carry away the excess water. A  
trap in the drain line is recommended and may be  
required by some local codes.  
Air may be drawn from a basement that is open  
to the home. All flexible ducting connected to the  
DH90 should be UL listed.  
A short piece of flexible ducting on all DH90 duct  
connections is recommended to reduce noise  
and vibration transmitted to rigid ductwork in the  
structure. Ducting the DH90 as mentioned requires  
consideration of the following points:  
The drain line should be connected to the 3/4" male  
pipe thread adaptor on the front of the DH90.  
Care should be taken to install the drain line with  
a continuous slope of 1" per 10' to assure proper  
water removal.  
Duct Sizing: For total duct lengths up to  
25', use a minimum 10" diameter round or  
Figure 1: Ducting to isolated areas.  
W8150  
Controller  
Fresh air intake  
EARD6  
Supply air  
Motorized  
damper  
Ducting to isolated areas  
Indoor air  
return  
 
For HVAC Installer Only • Installation Guide  
equivalent rectangular. For longer lengths,  
use a minimum 12" diameter or equivalent.  
Grills or diffusers on the duct ends must  
not excessively restrict airflow.  
structure. This helps prevent dirty and  
humid air from entering elsewhere.  
Exhaust fans are recommended in the  
bathrooms and kitchen.  
Isolated Areas: Effective dehumidification  
may require that ducting be branched to  
isolated, stagnant air flow areas.  
An insulated 6" diameter duct is generally  
sufficient to provide up to 75 CFM of outside air.  
Large quantities of outside air will impact DH90  
performance positively or negatively, depending  
upon the inside and outside air conditions.  
Use 8" or larger diameter branch ducting to each  
of two or three areas, use 6" or larger to each of  
four or more areas. Provisions must be made to  
provide airflow from supply locations to central  
return location. Proper air distribution is important  
to ensure even humidity control throughout the  
structure.  
The outside air duct should be connected to the 6"  
round collar on the side of the unit. The amount of  
outside air can be restricted by the blade damper  
in the 6" collar. The actual amount of ventilation  
air being delivered through the ventilation ducts  
must be measured in each installation. Refer to the  
instructions provided with the W8150 Ventilation  
Control for proper setup instructions.  
4.4B Ducting for Fresh Air — Option  
Fresh air may be brought into the structure by  
connecting an insulated duct from outside the  
structure to the 6" inlet of the DH90. Advantages  
of this form of ventilation include:  
4.4C Installation in a Basement or Crawl Space  
with an Existing Forced Air HVAC System  
1. Outside air is filtered before entering the  
building.  
Install a separate 10" return for the DH90 in a central  
area of the structure. Optional: Duct the supply of  
the DH90 to a 10" x 10" x 10" tee/damper, adjusted  
to 20% open to the basement. Duct the other side  
of the tee to the air supply of the existing HVAC  
system with a backdraft damper. Connect a duct  
from outside to the 6" collar of the DH90 if you  
wish to provide ventilation air. See Figure 2.  
2. Outside air will be dehumidified before  
entering if the DH90 is running in  
dehumidification mode.  
3. Drawing air from outside and blowing  
inside aids in slightly pressurizing the  
Figure 2: Basement or crawlspace installation.  
Indoor  
Heating A/C  
air return  
W8150 Controller  
return air  
Heating A/C supply air  
Dry air to basement  
Fresh air  
EARD6  
Inlet hood  
motorized  
damper  
 
DH90 Dehumidifier • For HVAC Installer Only  
W8150  
Controller  
EARD6  
Motorized  
damper  
Heating & A/C unit  
Fresh air intake  
Supply air  
Indoor air  
return  
Indoor air  
supply  
Indoor air  
return  
Figure 3: Attic Installation.  
Instead of installing a separate return to the DH90,  
and if the existing system has multiple returns,  
it is possible to select one to disconnect from  
the existing forced air system and use it for the  
dedicated DH90 return. Always select a return from  
a central location in the structure in an area that is  
always open to the rest of the structure. Do not use  
a return from a room that may have its door closed  
much of the time.  
The preferred method of installation is to create a  
separate return for the DH90 in a central area of  
the structure. Duct the supply of the DH90 to the  
air supply of the existing HVAC system. Connect  
an insulated duct from outside to the 6" collar of  
the DH90 if you wish to provide fresh air. Adjust a  
damper in the duct to provide the desired amount  
of fresh air. See Figure 3.  
4.4E Installation in a Structure with No Existing  
Forced Air HVAC System  
4.4D Installation in an Attic with an Existing  
Forced Air HVAC System  
When installing the DH90 in a structure that does  
not have a forced air HVAC system, a single return  
for the DH90 should be installed in central open  
area of the structure.  
ImPORTANT: ALWAYS install a catch pan  
with a drain or float interrupt for condensate  
under the DH90 in an attic or condensate  
may damage the living space below.  
DO NOT locate the return in a bathroom or a  
kitchen. The supplies of the DH90 should be  
located in the remote areas of the structure (such  
as bedrooms, den, etc.). By ducting this way, the  
air inside the structure will circulate through the  
DH90 to be filtered and dehumidified.  
The interrupt switch should be installed in series  
with the field wire that connects the blue lead  
from the DH90 to the dehumidistat. If overflow  
occurs, this switch opens the compressor control  
circuit and stops water production before the  
catch pan overflows. The DH90 will continue to  
ventilate or circulate air as normal, but will not  
dehumidify until this switch closes.  
6" diameter duct is recommended for branches to  
the bedrooms, 8" diameter duct is recommended  
for branches to larger areas. Connect an insulated  
duct from outside to the 6" collar of the DH90 if  
you wish to provide ventilation. See Figure 4.  
 
For HVAC Installer Only • Installation Guide  
W8150  
6. Wiring Diagrams  
Controller  
EARD6  
Motorized  
damper  
DH90  
Exhaust  
Air  
White  
Red  
Yellow  
Blue  
Green  
Fresh air  
Inlet hood  
Indoor air  
return  
Figure 4: Install with no forced air HVAC system.  
24VAC for powered  
Humidistat  
4.5 Noise Abatement  
OUTDOO  
R
HUMIDITY  
SETTING  
15%  
TEMPERA  
TURE  
-30  
-20  
-10  
F
F
C
-25  
C
20%  
Humid  
ity Co  
d'humi  
0
F
F
-20  
-10  
-5  
C
C
ntrol  
25%  
+10  
+20  
F
30%  
Régu  
F
lateur  
C
dité  
Ove  
r
35%  
20  
Over  
0
C
40%  
A length of 10' or more of acoustical flex ducting  
on the outlet of the DH90 will reduce air noise from  
the fan. A length of flexible ducting on all DH90  
duct connections is recommended to reduce noise  
transmitted to rigid ductwork in the structure.  
Dehumidistat  
Figure 5: Dehumidistat only—No fresh air ventilation.  
5. maintenance  
Figure 6: Dehumidistat including fresh air ventilation.  
5.1 Air Filter  
Ventilation damper  
The DH90 is equipped with a MERV 11 media  
filter. This filter should be checked every three  
months and replaced every six months. Operating  
the unit with a dirty filter will reduce dehumidifier  
capacity and efficiency and may cause the com-  
pressor to cycle off and on unnecessarily on the  
defrost control.  
XFMR  
R
W8150A  
C
CAUTION: Operate the unit only with a  
genuine Honeywell filter installed to assure  
proper performance of the unit.  
Damper  
DH90  
5.2 Optional Fresh Air Intake  
White  
Red  
Yellow  
Blue  
Green  
Check and clean the screen on the outdoor fresh  
air intake port seasonally. The screen may become  
plugged during the seasons when there are many  
particles in the outdoor air.  
Remote  
24vac for  
Powered  
Outdoor  
Humidity  
emperatur  
e
T
-20  
Setting  
15%  
f
-30  
-25  
-20  
-10  
-5  
c
c
-10  
f
f
f
20%  
Humid  
Régula  
0
ity con  
c
c
trol  
teur d'h  
25%  
+10  
+20  
over 20  
30%  
35%  
f
umidit  
c
c
é
f
over  
0
40%  
Humidistat  
Ventilation  
Override  
Switch  
Dehumidistat  
 
DH90 Dehumidifier • For HVAC Installer Only  
6.1 Choose the correct wiring diagram based on HVAC system  
HVAC  
HVAC  
R
C
W
Y
G
R
C
W1  
W2  
Y1  
Y2  
G
W8150A  
W8150A  
GF  
RC  
CC  
CH  
GF  
RC  
CC  
CH  
W
W
G
T
G
T
R
RC  
W
Y
G
R
RC  
C
W
1
W2  
Y1  
Y2  
G
System  
System  
Heat  
Heat  
AM  
AM  
Fan  
Fan  
Tue  
Wake  
Room  
Tue  
Wake  
Room  
Auto  
DST  
Auto  
DST  
M19994  
M19996  
Figure 7: Single transformer, conventional system.  
Figure 9: Multi-stage conventional system.  
Figure 8: Dual transformer, conventional system.  
Figure 10: Wiring heat pump without emergency heat.  
HVAC  
HVAC  
HEATING  
COOLING  
R
C
Y
G
O
R
C
W
R
C
Y
G
W8150A  
W8150A  
GF  
RC  
CC  
CH  
G
R
C
C
F
C
C
H
W
W
G
T
G
T
R
R
C
W
Y
G
O/B  
R
RC  
W
Y
G
System  
Heat  
AM  
System  
Heat  
Fan  
AM  
Tue  
Wake  
Room  
Auto  
DST  
Fan  
Tue  
Wake  
Room  
Auto  
DST  
M19997A  
M19995A  
 
For HVAC Installer Only • Installation Guide  
HVAC  
W2  
TIPS:  
Ventilation control reads new dial setting only  
when test button is pushed or power is cycled.  
R
C
Y
E
G
O
To ensure dial settings are read, push test  
button after any changes are made.  
W8150A  
For single bedroom homes, set the bedrooms  
dial to 2 (this may result in more ventilation than  
the minimum required).  
G
R
C
C
F
C
C
H
For homes having more than five bedrooms  
and only a single ventilation system, set the  
bedrooms dial to 5 (this may result in less  
ventilation than the minimum required).  
W
G
T
For conditioned square feet, set area (sq ft) dial  
to the nearest value.  
R
C
W
1
Y
1
W
2
E
G
O/B  
System  
Heat  
For airflow, set airflow (cfm) dial to the nearest  
value.  
AM  
Fan  
Tue  
Wake  
Room  
Auto  
DST  
Vaulted ceilings do not need to be considered  
when setting this control.  
M19998A  
For homes with multiple systems: Honeywell  
recommends a ventilation control and fresh  
air intake for each system. Measure ventilation  
airflow for each system independently. Refer to  
Multi-system Setup Example for further details.  
Figure 11: Wiring heat pump with emergency heat.  
7. Parts List  
For replacement parts call: 1-800-345-6770.  
DH90A1007 — DH90 Dehumidifier  
EARD6 — Motorized Damper  
50018994-001 — 14" x 14" x 1" MERV 11 Filter  
50018995-001 — 10" Back Draft Damper  
W8150A 1001  
Date installed:________________________  
Ventilation Limit*  
GF  
RC  
R
24 VAC  
C
60%  
1
2
100%  
XFRM  
ASHRAE 62.2  
62-1999  
HVAC CC  
CH  
DMP  
DMP  
AUX  
AUX  
REM  
REM  
Damper  
Ventilation  
Installer  
Test  
Standard  
W
ERV/Fan  
Stat GT  
Timer/Switch  
_________  
bedrooms  
_________  
_________  
airflow (cfm)  
area (sq. ft.)  
Record settings above  
Honeywell  
Golden Valley, MN 55422 www.honeywell.com/yourhome  
Para español ver las instrucciones  
50001159-001 Rev.  
A
or call 1-800-468-1502  
*See Instructions Voir mode d'emploi en français inclus  
8. Setting the control  
1. Be sure power is turned on.  
Date installed:________________________  
Ventilation Limit*  
W8150A 1001  
2. Set the Ventilation Standard on the control.  
3. Set the bedrooms dial.  
GF  
RC  
R
24 VAC  
XFRM  
C
60%  
1
2
100%  
ASHRAE 62.2  
62-1999  
HVAC CC  
CH  
DMP  
DMP  
AUX  
AUX  
REM  
REM  
Damper  
Ventilation  
Installer  
Test  
Standard  
W
ERV/Fan  
Stat GT  
4. Set the area (sq ft) dial.  
Timer/Switch  
_________  
bedrooms  
_________  
_________  
airflow (cfm)  
area (sq. ft.)  
Record settings above  
5. Set the airflow (cfm) dial.  
6. Press the test button and observe the lights:  
green light is flashing.  
The dial settings meet the chosen standard.  
Red light is flashing.  
There is not enough fresh air delivered  
to meet the requirements of the selected  
standard. See Troubleshooting section.  
7. Record settings on the label inside the cover  
as shown in the diagram.  
 
DH90 Dehumidifier • For HVAC Installer Only  
9. Service  
CAUTION: Servicing the DH90 with its high pressure refrigerant system and high voltage circuitry  
presents a health hazard which could result in death, serious bodily injury, and/or property damage.  
Service should only be performed by a qualified service technician.  
9.1 Troubleshooting  
4. Defective compressor.  
5. Defrost thermostat open.  
Nodehumidification,neitherfannorcompressor  
run with fan switch and ventilation timer OFF.  
6. Optional Condensate Pump Safety Switch  
open.  
1. Unit unplugged or no power to outlet.  
2. Humidity control set too high or defective.  
3. Loose connection in internal or control wiring.  
4. Defective Compressor relay.  
Fan runs when there is a call for dehumidifica-  
tion and the ventilation control is OFF, but the  
compressor cycles on and off too frequently.  
1. Low ambient temperature and/or humidity  
causing unit to cycle through defrost mode.  
5. Defective control transformer.  
6. Low pressure control open.  
2. Defective compressor overload.  
3. Defective compressor.  
7. Optional Condensate Pump Safety Switch  
open.  
4. Defrost thermostat defective.  
5. Dirty air filter(s) or airflow restricted.  
No dehumidification, compressor does not run  
but fan runs when there is a call for dehumidi-  
fication and the ventilation control is OFF.  
6. Low refrigerant charge, causing defrost  
control to cycle.  
1. Defective compressor run capacitor.  
2. Bad connection in compressor circuit.  
3. Defective compressor overload.  
7. Bad connection in compressor circuit.  
Fan does not run with fan switch in either  
position.  
10  
 
For HVAC Installer Only • Installation Guide  
Fan does not run with ventilation activated.  
Compressor runs briefly but cycles on & off  
with humidity control turned to ON.  
Unit Test to determine problem:  
1. Detach field control wiring connections  
from main unit.  
1. Loose connection in fan circuit.  
2. Obstruction prevents fan rotation.  
3. Defective fan.  
2. Connect the yellow and green pigtails  
from the main unit together; only the  
impeller fan should run. Disconnect the  
wires.  
4. Defective fan relay.  
3. Connect the yellow and blue pigtails from  
the main unit together; the compressor  
and impeller fan should run.  
5. Defective fan capacitor.  
Evaporator coil frosted continuously, low de-  
humidifying capacity.  
4. If these tests work, the main unit is  
working properly. You should check the  
control panel and field control wiring for  
problems next.  
1. Defrost thermostat loose or defective.  
2. Low refrigerant charge.  
5. Remove the control panel from the  
mounting box and detach it from the  
field installed control wiring. Connect the  
blue, yellow, and green wires from the  
control panel directly to the corresponding  
colored pigtails on the main unit.  
Leave the violet, white, and red wires  
disconnected!  
3. Dirty air filter(s) or airflow restricted.  
Unit not providing ventilation.  
1. Check control wire connections (check  
connections at fresh air damper also).  
2. Defective fresh air damper.  
3. Dirty air intake. Clean outside intake hood.  
6. Turn on the fan switch; the impeller fan  
should run. Turn off the fan switch.  
Unit removes some water, but not as much as  
expected.  
7. Turn on the humidity control; the  
compressor and impeller fan should run.  
1. Air temperature and/or humidity have  
dropped.  
8. If these tests work, the problem is most  
likely in the field control wiring.  
2. Humidity meter and or thermometer used  
are out of calibration.  
9.2 Refrigerant Charging  
3. Unit has entered defrost cycle.  
4. Air filter dirty.  
If the refrigerant charge is lost due to service or a  
leak, a new charge must be accurately weighed in.  
If any of the old charge is left in the system, it must  
be recovered before weighing in the new charge.  
Refer to the unit nameplate for the correct charge  
weight and refrigerant type.  
5. Defective defrost thermostat.  
6. Low refrigerant charge.  
7. Air leak such as loose cover or ducting  
leaks.  
9.3 Compressor/Capacitor Replacement  
8. Defective compressor.  
9. Restrictive ducting.  
This compressor is equipped with a two terminal  
external overload and a run capacitor, but no start  
capacitor or relay.  
10. Optional Condensate Pump Safety Switch  
open.  
CAUTION-ELECTRICAL SHOCK HAZARD:  
Electrical power must be present to perform  
some tests. These tests should be performed  
by a qualified service person.  
11  
 
DH90 Dehumidifier • For HVAC Installer Only  
Warranty Information  
Honeywell warrants this product, excluding battery, to be free from defects in the  
workmanship or materials, under normal use and service, for a period of five (5)  
years from the date of purchase by the consumer. If at any time during the war-  
ranty period the product is determined to be defective or malfunctions, Honeywell  
shall repair or replace it (at Honeywell's option).  
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS  
PRODUCT.THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WAR-  
RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS  
HEREBY LIMITED TO THE FIVE-YEAR DURATION OF THIS WARRANTY. Some states  
do not allow limitations on how long an implied warranty lasts, so the above limita-  
tion may not apply to you.  
If the product is defective, Contact your installing contractor for return information.  
This warranty gives you specific legal rights, and you may have other rights which  
vary from state to state.  
This warranty does not cover removal or reinstallation costs.This warranty shall  
not apply if it is shown by Honeywell that the defect or malfunction was caused by  
damage which occurred while the product was in the possession of a consumer.  
If you have any questions concerning this warranty, please write Honeywell  
Customer Relations, 1985 Douglas Dr, Golden Valley, MN 55422 or call 1-800-468-  
1502. In Canada, write Retail Products ON15-02H, Honeywell Limited/Honeywell  
Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.  
Honeywell's sole responsibility shall be to repair or replace the product within the  
terms stated above. HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAM-  
AGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES  
RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY,  
EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do  
not allow the exclusion or limitation of incidental or consequential damages, so this  
limitation may not apply to you.  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
Golden Valley, MN 55422  
Honeywell Limited/Honeywell Limitée  
35 Dynamic Drive  
Toronto, Ontario M1V 4Z9  
Thank you for choosing a high performance  
Honeywell Indoor Air Quality product  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
® U.S. Registered Trademark.  
© 2006 Honeywell International Inc.  
69-1951 M.S. 06-06  
1ꢀ  
 

Haier Dishwasher DW12 PFE1ME User Manual
Hamilton Beach Coffeemaker 47214 User Manual
Harbor Freight Tools Battery Charger 45005 User Manual
Harbor Freight Tools Portable Generator 94192 User Manual
Harbor Freight Tools Saw 93827 User Manual
Heat Glo LifeStyle Indoor Fireplace st 42tvfl User Manual
Heat Glo LifeStyle Indoor Fireplace XLR N CE User Manual
Honeywell Weather Radio TS34C User Manual
Husqvarna Brush Cutter 249953 User Manual
IBM Computer Monitor 9511 A User Manual